022
Before starting up a generator, check that:
batteries are correctly connected
earthing has been properly established
all electrical connections have been made
the installation of the group complies with the conditions established by the manufac-
turer and the legislation in force.
oil levels are correct
antifreeze levels are correct
fill the fuel tank with at least 20%, but not more than 90%.
start the generator in the controller for 1 minute at no load
after 3 months without functioning: it is recommended to add an antibacterial product
to the fuel
after 6 months of non-operation: must proceed as defined by the engine manufactur-
er, regarding long-term storage.
STARTING UP06.
If the generator is to be stored before to use, adequate facilities must be provided, free of
dust and moisture, and the unit must be protected from chemical agents that could
damage it or could damage any of its components.
If storage is expected for more than five months, it is advisable to remove engine oil and
filters until the equipment is used. Battery must be turn off.
5.1. MOVING AND STORAGE
Without hoist ring
Containers – ISO cornersWith hoist ring