INSTALLATION AND USAGE MANUAL
Manufacturer: GRYFIT TECHNIK Sp. z o.o. – ul. Łąkowa 11 – 95-050 Konstantynów Łódzki
LX-5 FIRE DAMPERS
WITH FDG-WT OR BELIMO ACTUATORS
EI (v
e
– h
o
– i o) S
CERTIFICATE OF CONSTANCY OF PERFORMANCE
n
o
1488
-
CPR
-
/
W
1- INSTALLATION
Installation should be carried out by professional who has been trained in GRYFIT components installation.
1.1- OVERALL DIMENSION OF THE INSTALLATION OPENING
To install the damper properly the recommended overall dimension of the installation opening is (L+90) x (H+90) mm if the
damper is installed in the brick, concrete wall or concrete horizontal partition and (L+70) x (H+70) mm if it is installed in the
light-weight wall. Smaller overall dimension of the installation opening is allowed however in that case installation should
be carried with particular care - the clearance between damper body and wall should be entirely filled with the grout or
heat resisting sealant or filler. The minimum overall dimension of the installation opening is determined by the damper
flange size.
1.2- FIXING AND INSTALLATION
Close the damper before installation. Place the damper axially in the installation opening. In order to provide partition walls
with fire resistance, it is absolutely necessary to observe the mortaring border line which is marked on the label on the
damper casing. In case of installation in the brick or concrete walls, facing should be made of masonry mortar or non-
shrink grout. In case of installation in the plaster-cardboard walls, the drawings on the next pages should be followed.
NOTES:
a) Damper mechanism must be always accessible for inspection and maintenance keep free space of 200 mm
between damper mechanism and nearest building partition or any other obstacle which may restrict the
access to the damper mechanism.
b) It is highly recommended to use the UM optional installation brackets to facilitate installation. Installation
brackets are delivered flat and have to be bended before installation of the product.
c) It is absolutely necessary to respect damper installation mortaring border line which is clearly marked on the
label to be found on the damper casing.
d) While installing it is impermissible to grime a control mechanism of the damper with mortar, sealant, filler,
glue or paints. The control mechanism of the damper has to be protected until the masonry and completion
work is finished.
e) The damper blade has to be closed during installation and until mortar, sealant, filler or glue is hardened. The
damper casing cannot be burdened during installation otherwise it can result in deformation of the casing
and damage of the damper blade.
1.3- INSTALLATION METHOD
The dampers with dimensions up to LxH=1000x1000 can be installed both with their blade axis positioned horizontally and
vertically. As regards the larger dampers it is recommended to install them with their blade axis positioned horizontally, or
to consult with our service center about installation with the blade axis positioned vertically.
1.3.1- APPROVED BUIDLING PARTIONS IN WHICH THE GRYFIT LX-5 DAMPERS CAN BE INSTALLED
The dampers can be installed in the following vertical and horizontal building partitions:
Concrete wall with a thickness not smaller than 125 mm,
Hollow brick walls with a thickness not smaller than 125 mm,
Concrete masonry walls with a thickness not smaller than 125 mm,
Plasterboard walls installed with metal studs framing approved to fire resistance class not less than EI 120 with a
thickness not smaller than 125 mm,
Concrete floor with a thickness not smaller than 150 mm.
Question and Answer IconNeed help?

Do you have a question about the Gryfit LX-5 and is the answer not in the manual?

Summary

INSTALLATION AND USAGE MANUAL

1- INSTALLATION

General instructions for installing GRYFIT fire dampers by trained professionals.

1.1- OVERALL DIMENSION OF THE INSTALLATION OPENING

Specifies required dimensions for the installation opening based on wall type and materials.

1.2- FIXING AND INSTALLATION

Details the process of fixing the damper and requirements for partition walls, including notes on access.

1.3- INSTALLATION METHOD

Explains different methods for installing dampers based on size and orientation, and approved partition types.

1.3.1- APPROVED BUILDING PARTITIONS

Lists approved partition types and minimum thickness for GRYFIT LX-5 damper installation.

1.3.2- BRICK OR CONCRETE WALL

Installation specifics for brick or concrete walls, including opening dimensions and mortar filling.

1.3.3- PLASTER-CARDBOARD WALL

Installation instructions for lightweight plaster-cardboard walls, emphasizing careful clearance filling.

1.3.4- FLOOR AND CEILING

Procedures for installing dampers in floors and ceilings using appropriate mounting elements.

1.4- CONNECTION TO VENTILATION DUCT

Guidelines for connecting the damper to ventilation ducts, ensuring proper operation and avoiding damage.

1.5- ELECTRICAL CONNECTION

Instructions for making electrical connections and wiring diagrams for various actuator types.

1.5.1-FDG-WT-5 AND FDG-WT-8 ACTUATORS

Provides actuator characteristics and electrical wiring diagrams for FDG-WT series actuators.

1.5.2 - BELIMO ACTUATORS

Details actuator characteristics and electrical wiring diagrams for Belimo actuator models.

2- USAGE INSTRUCTION

2.1- OPEN DAMPER - THE STAND-BY POSITION

Explains how the damper blade remains open in stand-by mode, powered by the electrical actuator.

2.2- CLOSURE OF THE DAMPER - TURNING INTO THE SAFETY POSITION

Details the mechanisms and conditions for the damper's automatic closure into the safety position.

2.3- OPENING OF THE DAMPER - RETURN TO THE STAND-BY POSITION

Describes how to reopen the damper to its stand-by position via electrical supply or manual control.