EasyManua.ls Logo

GST I-9403 - Programming; Wiring Diagram

GST I-9403
5 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30308397 Page 2 Issue 1.01
Tone, single/dual address mode and consumption
mode can be set as the same as programming the
parameter of a module by P-9910B programmer. Refer
to Table 1 for parameters and P-9910B Installation and
Operation Manual for details.
Working mode can be set as same as programming
device type by the programmer, refer to P-9910B
Installation and Operation Manual for details.
Sounder and strobe (defaulted): 24;
Sounder only: 20;
Strobe only: 21.
In single address mode, the sounder strobe will
sound the preset tone with flash frequency 1.4×
(1±20%)Hz when activated.
In dual addresses mode,
The sounder strobe will sound the pre-alarm
tone (refer to Table 1) with flash frequency
0.7×(1±20%)Hz when activating the first address;
The sounder strobe will sound a preset tone
(refer to Table 1) with flash frequency
1.4×(1±20%)Hz when activating the second
address;
The sounder strobe will sound the preset tone
(refer to Table 1) with flash frequency 1.4×
(1±20%)Hz when activating the first and second
address together.
Wiring diagram
Fig.5 shows that the sounder strobe is
loop-powered.
Sounder Strobe
Z1
D2
D1
Z2
Z1
Z2
Fig. 5
Fig. 6 shows that the sounder strobe is
supplied by an external 24V power.
Sounder Strobe
Z1
D2
D1
Z2
Z1
Z2
D1
D2
Fig. 6
An example shows that how to set the sounder
strobe addressed 25 as dual addresses, tone 15 and
normal consumption mode.
Switch on the P-9910 programmer, input the password
and press the Function key and number 3. Enter 63 and
the Program key. The setting is successful when P
appears on the display. The sounder strobe is now to be
programmed Address No. 25 and 26.
Table 1 shows tone mode, programming method,
consumption for the sounder strobe (Single address,
tone 14 and normal consumption are defaulted).
Table 1
Tone
Programming
method
Consump-
tion mode
01
Single
address
Power-
Saving
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
01
Dual
addresses
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
01
Single
address
Normal
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
01
Dual
addresses
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16