7.1.4.1 The ou tdoor fan control when refrigerating or dehumidifying
After the compressor is started for 5 seconds,
the outdoor fan
is
started according to the
temperature conditions of the outdoor environment.
The outdoor fan control when heating
7.1.4.2
Domestic air conditioner
21
<40 4060 60
500 600 700
600 700 850
850 900 900
when cooling
compressor
frequency
( Hz)
Twh(℃)
900
23
23-29
2940
40
<60 6090 90
800 900 900
700 800 850
16 700
when heaating
compressor
frequency
(Hz)
Twh(℃)
10
10-16
Functions and control
In 3 minutes,
After 3 minutes,The wind speed control is related to the frequency of the compressor and the temperature
conditions of the outdoor environment.
After the compressor is started for 5 seconds,
the outdoor fan
is
started according to the
temperature conditions of the outdoor environment.
In 3 minutes,
Twh℃) Twh <10 10< Twh <16 Twh16
850 650 400
Twh℃) Twh <23 23<Twh<29 Twh29
500 650 800
After 3 minutes,The wind speed control is related to the frequency of the compressor and the temperature
conditions of the outdoor environment.
Heating
Cooling\Dry