10.4.6 Over-current of the compressor
Outdoor Display: LED1 flash 3 or 24 or 25 times
Method of The current of the compressor is too high
Malfunction
Detection
Malfunction when the IPM Module is damaged
Decision or the compressor is damaged.
Conditions power supply voltage is too low or too high
Supposed
Faulty IPM Module
Causes
Faulty compressor
Faulty power supply
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller, If malfunctions
are reported before or upon the compresso
r
being started up,
IPM Module is damaged and
needs replacing.
Repair the power supply
The system may have been over or under
charged with gas, which can be judged through
the pressure of the measuring system.
YES
NO
Yes
NO
The compressor is started normally, but
malfunctions are reported after it has
run for some time. Check the powe
r
supply is too low or too high
NO
Service diagnosis
Domestic air conditioner
41

Other manuals for Haier 2U50S2SM1FA-3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier 2U50S2SM1FA-3 and is the answer not in the manual?

Haier 2U50S2SM1FA-3 Specifications

General IconGeneral
BrandHaier
Model2U50S2SM1FA-3
CategoryAir Conditioner
LanguageEnglish

Related product manuals