10.4.11 Loss of synchronism detection 
Inverter side current detection is abnormal 
Outdoor Display  
LED1 flash 18 times   
                  LED1 flash 19 times 
Method of      The position of the compressor rotor can not detected normally 
Malfunction
Detection
Malfunction       when the wiring of compressor is wrong or the connection is poor;
Decision    or the compressor is damaged 
Conditions
Supposed     
 Faulty    The wiring of compressor 
Causes     
 Faulty    compressor
 Faulty    PCB 
       
Troubleshooting  
* Caution   
Be sure to turn off power switch before connect or disconnect connector, or parts 
damage may be occurred. 
Within  3  minutes  after  the  machine  is
supplied with power and turned on with
the  remote  controller,  check  whethe
the compressor can start up 
1.  The  wiring  of  compressor  is  incorrect 
or the connection is poor; 
2. The compressor is damaged 
At  first,  the  compressor  start  up  ,soon  the 
compressor  stopped  with  the  LED1  on  the 
outdoor PCB blinks
1Hz 19/18 times 
IPM  Module  is  damaged  and  needs 
replacing.
the  Malfunctions  exist  also,  the 
compressor  is  damaged  replace  a 
new one 
YES 
NO
YES 
Malfunction unsolved 
Maybe there is some disturbance 
  Service diagnosis
 
Domestic air conditioner
 
47