>a__WcU[S^ <[c >a`V[e[a`Wc
2m continuously
13 13(0DH) 31D Solenoid valve
abnormal
Solenoid valve act
incorrectly 3 times
continuously
14 76(4CH) 15D Discharging temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
15 05(05H) 17D EEPROM abnormal EEPROM data missing Run as the
default
value
16 84(54H) 26D Pressure
abnormal(low
pressure)
Low pressure switch acts in
normal running
17
8050H
15D Compressor overheat the discharging
temperature is higher than
120degree
Resumable
if lower
than
100degree
18
120CH
23D Abnormal mode Indoor operation mode is
different with the running
indoor unit.
19
754BH
18D Outdoor coil
B(suction temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
20
774DH
15D Outdoor discharging
B(oil temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
shows resumable fault, shows it is not resumable fault.
-159-