12.2 AU422XIBAA
cooling capacity (KW) changing with indoor/outdoor
temperature
8.0
10.0
12.0
14.0
16.0
18/14 20/15 22/16 25/18 27/19 30/22 32/23
indoor D.B./W.B.
cooling capacity
18
20
25
32
35/24
40
43
46
power comsumption changing with indoor/outdoor temperature
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
1
8
2
0
2
5
3
2
3
5
/2
4
4
0
4
3
4
6
indoor D.B./W.B.
power consumption (kW)
18/14
20/15
22/16
25/18
27/19
30/22
32/23
The data is measured in the normal condition: outdoor DB/WB 35/24, indoor DB/WB 27/19
High drop and long pipe: capacity modification curves
AU422XIBAA
15
12.5
10
7.5
5
2.5
0
-2.5
-5
-7.5
-10
0 5 7.5 10 12.5 15 17.5 20
100%
88%
98% 96%
94%
92%
90%
Equivalent total distance between indoor and outdoor unit of one way (m).
The standard installation piping length and drop should within this range.
Drop between the indoor and outdoor unit(m).
H>0: Outdoor unit higher than indoor unit