Service diagnosis   
 
 42   Domestic air conditioner 
 
10.3.11 Loss of synchronism detection 
Inverter    side current detection is abnormal 
Outdoor Display   
LED1  flash 18 times  
  LED1  flash 19 times 
 
Method of                The position of the compressor rotor can not detected normally 
Malfunction 
 
Detection 
 
Malfunction            when the wiring of compressor is wrong or the connection is poor;
 
 
Decision        or the compressor is damaged 
 
Conditions 
 
Supposed 
Ƶ
  Faulty  The wiring of compressor 
 
Causes 
Ƶ
  Faulty  compressor
 
Ƶ
  Faulty  PCB 
 
 
Troubleshooting    
* Caution   
Be sure to turn off power switch before connect or disconnect connector, or parts 
damage may be occurred. 
 
 
 
 
 
 
 
 
 
 
 
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller, check whethe
the compressor can start up 
1. The wiring of compressor is incorrect 
or the connection is poor; 
2. The compressor is damaged 
At first, the compressor start up ,soon the 
compressor stopped with the LED1 on the 
outdoor PCB blinks˄1Hz˅19/18 times 
IPM Module is damaged and needs 
replacing. 
 
the Malfunctions exist also, the 
compressor is damaged replace a 
new one 
YES 
NO 
YES 
Malfunction unsolved 
Maybe there is some disturbance