Installations
Domestic air conditioner
32
Supposed                 
■
 
  IPM protection dues to the compressor faulty   
Causes                     
■
   
IPM protection dues to faulty PCB of IPM module                 
■    Compressor wiring disconnected 
 
Troubleshooting       
* Caution   
Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred.   
NO 
YES 
    Electrify the machine again and turn it on with 
the rem ote controller ,If ma lfunctions are reported 
before or upon the compressor being started up.
IPM Mod ule is damaged  
and needs replacing.
The compressor is started nor mally , 
but malfunctions are reported after it 
has run for some time. 
1、The system may have been over(like,capillary clogging  or electronic expansion valve faulty ) or under 
charged with gas, which can be judged through the pressure of the measuring system. 
2、The shaft of compressor is seized and the compressor needs replacing.
Test IPM module resistance  between P and U,V,W .
Then test IPM module resistance between N and U,V,W. 
The resistances range  are between 1MΩ with 10MΩ.and they 
are similar.
NO 
YES 
10.3.6 Over-current of the compressor 
 
Outdoor Display:      LED1    flash    3 or 24 or 25 times 
 
Method of                The current of the compressor is too high 
Malfunction         
 
Detection 
 
Malfunction            when the IPM Module is damaged 
 
Decision                  or the compressor    is damaged. 
 
Conditions              power supply voltage is too low or too high 
                         
Supposed                  ■    Faulty    IPM Module 
 
Causes                      ■    Faulty    compressor
 
■    Faulty    power supply 
               
 
Troubleshooting       
* Caution   
Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.