Installations
Domestic air conditioner
31
Check whether Terminal on the outdoor 
mainboard is well inserted. 
   it is normal
Reinsert the terminals
Electrify the machine again and turn it on in 
the Cool state with the remote controller. 
check whether the motor could run. 
Remove fan m otor  afte r  s witch off 
the power.Measure the resistances 
between black line (0V) and red 
line( 310V),between black line(0V) 
and white line ( 1 5 V) of the fan 
motor . 
NO
YES
The resistances are 
greater than 40KΩ
NO
YES
The motor of the outdoor unit is 
damaged and needs replacing.
NO
  the resistances between 0V 
and  310V,between 0V and 15V of 
the fan terminal of outdoor pcb are 
greater than 10MΩ.
The module pcb is 
damaged, replace it 
with a new one.
The outdoor pcb is 
damaged, replace it 
with a new one.
YES
The motor and 
outdoor pcb are 
well
YES
NO
10.3.5 IPM protection 
 
Outdoor display:      LED1    flash    2    times 
 
Method of             
IPM protection is detected by checking the compressor running condition and so on 
Malfunction             
Detection 
 
Malfunction               
■
   
The system leads to IPM protection due to over current
 
Decision                   
■
   
The compressor faulty leads to IPM protection 
 
Conditions               
■
 
  circuit component of IPM is broken and led to IPM protection