Commercial Air Conditioner   Model: AP*****EAA AU*****EAA 
15
temperature and Ts means setting temperature. 
Select running mode according to the following conditions at the first time to enter Auto mode: 
TrıTs- 3 ć          to select cooling mode (with setting temperature being Ts +3) 
Tr˘Ts- 3 ć        to select heating mode (with setting temperature being Ts) 
After the system entering auto run mode, the running mode can convert automatically 
according to variation of room temperature between cooling and heating. If the unit is in cooling 
mode, when the temperature arrives stop value, the compressor stops; the system will measure the 
temperature after compressor stops for 3 minutes. At this time, if Tr˘Ts-3ć, the unit will enter 
heating mode, or it will still be cooling mode. If the unit is in heating mode, when the temperature 
arrives stop value, the compressor stops; the system will measure the temperature after 
compressor stops for 3 minutes. At this time, if Tr˘Ts+3ć, the unit will enter cooling mode, or it will 
still be heating mode.   
If the unit is in heating mode, when indoor heat exchanger temperature is over 63ć, the unit 
will turn into cooling mode automatically, in 1 hour, the indoor heat exchanger temperature will not 
be limited, and heating operation will stop temporarily, 1 hour later, the system will adjust the 
working mode due to the above conditions. 
If the unit is in heating mode for the first time, compressor motor will start up, within 8 minutes the 
system will not measure indoor ambient temperature, the remote controller will be off.
2). Single Cooling type
Select running mode according to the following conditions at the first time to enter Auto mode: 
TrıTs+ 3 ć      to select cooling mode 
Tr˘Ts- 3 ć      to select blowing mode 
After entering Auto mode, the operation mode can be changed between cooling mode and fan 
mode according to indoor ambient temperature: if the unit now is in cooling mode, when Tr˘Ts-3,
the mode will be changed to Fan; if the unit is in Fan mode, when TrıTs+3, the mode will be 
changed to cooling mode. 
3. COOL mode control 
4-way valve being powered off, compressor run/stop will depends on the temperature 
difference between the room temperature and the set temperature. 
  TrıTs+1    compressor will run; 
  TrİTs-1    compressor will stop; 
Ts-1<Tr<Ts+1    compressor will stay in original state
Anti-freezed protection
When the unit has run for over 6 minutes after compressor starts up, if indoor coil temperature 
Tg<1ć last 1 minute, the compressor and the outdoor motor will stop; 9 minutes later after 
compressor stops and when indoor coil temperature rises to 10ć, the compressor and the outdoor 
motor will run again. 
run
stop
1
ˉ1
run
stop
7
7