7) High current protection in 3-phase fixed frequency models
Is three-phase circuit not 
balanced? Is supply voltage too 
low? Is supply voltage too low at 
compressor start-up?
yes
no
re-wiring
yes
Is compressor current more than overcurrent 
protection limit? Is current detecting circuit in 
good condition?
Confirm detecting circuit 
is abnormal,replace 
outdoor PCB
no
yes
yes
replace AC contactor
yes
if compressor is normal
no
Is resistance of compressor 
winding incorrect? Is it stuck?
yes
replace compressor
yes
if pressure is normal
no
Check: 1. Is a valve in system shut off;
2. Is piping clogged; 
3. Is system overfed; is there air in system;
4. (Cooling cycle) Is condenser dirty? Does outdoor fan motor run at low speed or stop?
5. (Heating cycle) Is evaporator or filter dirty? Does indoor fan motor run at low speed or stop?
6. Is ambient temperature too high? Is system overloaded?
Is power cable or compressor wire 
securely connected? Properly?
Modify power supply circuit
yes
Is AC contactor in 
poor contact?
Short connect that 
terminal
if failure disappear after 
PCB is changed
yes
no
replace PCB
yes
Solve problem 
accordingly
yes
Is an external alarm 
connected to the system?
8) External alarm
no
Is ALARM terminal in 
mainboard disconnected?
An external alarm is 
identified according to the 
list of fault codes
Commercial Air Conditioner Model: AP*****EAA AU*****EAA 