13) Fault in indoor fan motor
confirm the malfunction 
according to the fault code list
no
no
yes
no
yes
yes
no
no
yes
yes
yes
no
no
no
no
yes
yes
yes
yes
yes
no
no
Replace fan 
motor
no
no
yes
yes
Is power supply good?
yes
Is indoor status 
indication good?
Is fuse in good condition?
Replace fuse 
when there is no 
short-circuit
Is there any other 
broken component?
check any other 
reasons
Is output voltage of 
fan motor good?
Is fan capacitor 
in good 
condition?
Is fan motor winding 
resistor normal?
Wrong fault code. Check 
other possible causes. E.g. 
motor is stuck
Replace fan 
capacitor
Replace PCB
No. It's split winding type motor
Is it a PG motor? As in 
AS and AF indoor units
Is output voltage good 
when energized? Does fan 
motor run properly?
Is there DC voltage 
feedback from motor 
during running?
Signal detecting circuit has 
a problem. Replace PCB
Replace motor
Is front-end voltage of 
thyristor good?
Supply circuit has a 
problem. Replace PCB
Thyristor or control 
circuit has a problem. 
Replace PCB
Is front-end voltage 
of fan speed relay 
good?
Is voltage of fan speed 
relay coil 12VDC?
Supply circuit has a 
problem. Replace PCB
Controller chip has a 
problem. Replace PCB
Fan speed relay is 
broken, replace PCB
Is there any poor 
connection?
Reconnect
Commercial Air Conditioner Model: AP*****EAA AU*****EAA 