SERVICE MANUAL
Model: HA10TG20SW/S/B
17
Issue 2009-7-24
Rev. Ref0907S005V0
5-3.Defrosting Principle
1. A defrost cycle will start after an accumulated compressor run time of 4 hours.
2. Automatic Defrost
2.1 It could enter defrost after an accumulated compressor run time of 3~48 hours according to
ambinet temperature,door open–close
2.2 It will stop defrosting when defrost sensor temperature reach 12or the defrost time is up to
50 munutes.
2.3 If the defrost time does not reach 50 minutes,but the temperature reaches 12 ,the defrost
will be stopped immediately.
3. Rated defrost heater power :150W.
Note: It must be in rated voltage 115V/60Hz, above parameters is practical.