Indicator
Fig. 9-3
25
1.  Be sure power is off to the motor. 
2.  Disconnect the motor wires. 
3.  Place one ohmmeter lead on common and the other on start .The meter should show continuity. 
4.  Place one ohmmeter lead on common and the other on run. The meter should show continuity with 
less resistance. 
5.  Leave one meter lead on common and touch each remaining lead. Each should indicate continuity. 
6.
7.
MECHANICAL 
ELECTRICAL CHECK TO TEST FAN MOTOR: 
If a winding does not show continuity, the motor has failed and must be replaced. 
may be caused by excessive water. Lubrication can be washed out of permanently lubricate bearing.
If the motor needs replacing, replace the capacitor as well. 
Fan motors can fail for a number of reasons, including failure bearing loss due to a lack of lubrication. This 
If a motor fails, replace it with cimilar motor having 
the same rotation horse power, RPM and electrical
CONDENSER FAN BLADE LOCATION
Dimension “A” will be from 2” to 4” depending on the unit model number. Be sure to check this 
dimension    BEFORE removing the fan blade.
Note: When parts combination results in motor /blade interference ,the fan blade should be
located to provide 1/8” motor /blade clearance. 
RELAYS
ELECTRICAL OPERATION
Contactor coils are made with copper wires wrapped around a steel core. When energized, the coil
generates a magnetic field that moves the steel core to open or close the circuit contacts. Electrical
continuity indicates a good coil. Relay coils use specific voltage. Using a contactor with the wrong voltage
coil will prevent the system from operating properly. This problem is avoided when using  the proper
replacement part for a failed component.
characteristics.
Fig. 9-4
can generate enough heat to weld the contacts together. Physical examination of the contacts 
Relay contacts are switches and can become pitted or corroded, creating resistance. Resistance
  Central Air Conditioner Model: Cooling Only, 13SEER units