(7) Open alarm: Refrigerator door opened more than 180 seconds, the alarm buzzer alarm; 
the 3 time (0.5 seconds), if the door still opened, then the alarm 3 times every 30 seconds 
(0.5 seconds), until the switch is closed (i.e. door closed).。 
(8)  Power  failure  with  memory:  this  refrigerator  is  designed  with  power  failure  with  memory. 
Specific status prior to power failure will be kept when the refrigerator goes into power failure; 
power failure with memory: defrosting status, refrigerating, variable temperature and freezing 
temperature gear setting, quick-freeze, quick-cooling, intelligent. Power failure without memory: 
compressor protection, quick-freeze time, quick-cooling time. 
(9) Control of refrigerator lamp: when the refrigerator door opens, its lamp lights; when it is closed, 
the lamp is off. The refrigerator lamp automatically lights off when the refrigerator door keeps 
open for more than 7 minutes. 
(10) Fan/Damper control: when refrigeration is activated in the freezer compartment, the freezer 
fan and compressor work at the same time. When the refrigerator door opens, the freezer fan 
and  damper  stop  working  immediately.  The  compressor  is  under  normal  control  with 
compartment temperature until the refrigerator door is closed or the fan and damper return to 
normal control after 7 minutes. 
(11) Initial power-on status: the temperature of refrigerator compartment is set to be 3℃, -18℃  for 
the freezer compartment and  “BeverageCooling”  for the my zone temperature compartment 
when the refrigerator is initially powered on. The refrigerator will not start up if the refrigerator, 
my zone temperature and freezer temperature are between the starting temperature and the 
stopping temperature. It starts when the temperature returns to that at the starting point. 
(12) Display control: The display lights off if the refrigerator door is closed and the button is not 
activated within 30s. The display lights on when any button on the display panel is touched or 
when the refrigerator door opens. The LED lights off when the opening time is more than 30s. 
(13) Compressor protection: Startup of the compressor is permitted after it is put in shutdown for 7 
minutes. It enters into normal control upon completion of the 7-minute delay. 
Control principle of defrosting system 
*For initial power-on, defrosting begins when the compressor accumulatively works for 8hr. 
*The compressor and  freezer fan stop and  the  dampers close  during defrosting. When the 
temperature  of  defrosting  sensor  is  no  less  than  12℃,  the  defrosting  heater  strip  shall  be 
disconnected. 
*For entrance into defrosting, the defrosting heater strip exists defrosting after working for 10s if 
the temperature of defrosting sensor is no less than 12℃. 
*Forced defrosting: Open the door, locked, press the "Fridge" button, at the same time, 
press the "My zone" button 5 times, then press "Lock" button for 1 times. The display 
board displays "T2", began forced defrost.Defrosting exits when the defrosting sensor 
temperature reaches 12
℃
. The power of defrosting is 180W (rated voltage 220V). The 
deviation shall be within 10W.