The condensate trap and entire drain system attached to it (above the neutralizer) should be cleaned at
least once every year.
1)TurnoffthepowertotheEVO.
2)Placeabucketunderthecondensatetrap.Usecautionwhenremovingtheclean-outcap,as
the trap is full of condensate and it may be hot.
3)Removethecondensateclean-outcap,andbesurethe
bucket is under the open drain trap assembly to catch
the debris and water.
4)Rinseouttheclean-outcapinasinktoremoveanydirtorbuildupthatmayhaveaccumulated.
5)Condensatedrainassemblyshouldnowbecheckedfornon-restrictedowthroughoutthe
entire assembly.
6)Reinstalltheclean-outcaponthecondensatetrap.
7)TurnonthepowertotheEVO.
8)Makesurethehosefromthecondensatetrapisnotsubmergedtoofarintotheneutralizer,
there should be an air gap between the highest level of condensate and the outlet hose from the trap.
9)Monitorthecondensatedrainuntilowhasbeenestablished.
CONDENSATE TRAP CLEANING INSTRUCTIONS