SECTION 3 COMPONENT DESCRIPTIONS
StartupDelayMode
SystemIniJalizing
ReleasingAir
CollecJngAir/Water
StartupDelayMode
SystemIniJalizing
ReleasingAir
CollecJngAir/Water
StartupDelayMode
SystemIniJalizing
ReleasingAir
CollecJngAir/Water
StartupDelayMode
SystemIniJalizing
ReleasingAir
CollecJngAir/Water
Startup Delay Mode – appears for 10 minutes after APPT
evaporator shell temperature reads below 40F (4C) and
the foul gas pressure is higher than 80 PSIG (5.5 BARG).
System Initializing – appears after either the System
Reset key has been pressed or power is cycled to the
APPT while the Liquid Make-Up Level Sensor is reading
wet. APPT will stay in this mode until Liquid make-Up
Level Sensor reads dry. This prevents the heaters from
turning on until the evaporator shell has filled with liquid.
Collecting Air/Water – appears when the APPT is in
its normal operating of collecting noncondensible gas
and water.
Releasing Air – appears when the APPT is releasing
noncondensible gas.
DISPLAY MESSAGES FOR APPT