1
- 3.1Large Screen
- 2 Part Control Panel (Mainboard + Room Panel)
- Aspirator, Vantilator 6 Level Speed Control
- Automatic/Manuel Mode
- 3 Stage Heater Control
- Return Air Temperature Input (NTC 10K)
- Carbon dioxide Control (CO2 Transmitter Input)
- BMS Input (Dry Contact)
- Dirty Filter Input
- On/Off Damper Output
- Minimum ve Maximum Set Temperature Limit
- Weekly Program (for BCP-6-T)
Order Code:
Room Panel: BCP-6-X
X: T > Weekly Program
Mainboard: M1002
Warning
Please read the manual and following cautions before you begin installing the device.
Responsibility of accidents and damages caused by failure to observe the warnings in the manual belongs to
user. Operation on the device cause damage to device and system. In this case damaged device will be out of
warranty.
User Manual BCP-6-T v01 06/17
BCP-6-T/M1002 HRV CONTROLLER
Question and Answer IconNeed help?

Do you have a question about the HAVKON BCP-6-T and is the answer not in the manual?

Overview

The BCP-6-T/M1002 HRV Controller is a device designed for managing Heat Recovery Ventilation (HRV) systems, specifically those with mono-stage or EC fans. It consists of a mainboard (M1002) and a room panel (BCP-6-T) with a 3.1" large screen for user interaction.

Function Description

The controller offers comprehensive management of HRV systems, including:

  • Aspirator and Ventilator Control: Provides 6-level speed control for both aspirator and ventilator fans, allowing for precise airflow management.
  • Operating Modes: Supports both Automatic and Manual modes, giving users flexibility in how the system operates.
  • Heater Control: Features 3-stage heater control to manage auxiliary heating within the HRV system.
  • Temperature Sensing: Utilizes a Return Air Temperature Input (NTC 10K) for accurate temperature monitoring.
  • CO2 Control: Integrates with a CO2 Transmitter Input for carbon dioxide level monitoring and control, enabling demand-controlled ventilation.
  • Building Management System (BMS) Integration: Includes a BMS Input (Dry Contact) for seamless integration with external building management systems.
  • Filter Monitoring: Features a Dirty Filter Input to alert users when filter maintenance is required.
  • Damper Output: Provides an On/Off Damper Output for controlling air dampers.
  • Temperature Limits: Allows setting Minimum and Maximum Set Temperature Limits to ensure comfortable and safe operation.
  • Weekly Program: Supports a weekly programming feature (for BCP-6-T models) to schedule operations based on user preferences.

Important Technical Specifications

Environmental Specifications:

  • Operating/Storage Temperature: 0 ... +40°C for operation and 0 ... +50°C for storage (without condensation).
  • Relative Humidity: 0...95% r.H (without condensation).
  • Protection Class: Mainboard: IP 00; Room Panel: IP 20 (according to EN 60529).
  • Height: Up to 2000m.
  • Usage Environment: Must be used in non-flammable environments.

Electrical / Operating Specifications:

  • Power Supply: AC 230 V.
  • Power Consumption: 5VA.
  • Connection: 1.5mm² terminal.

Outputs (ÇIKIŞLAR):

  • Vantilator Output: 6 Stage (Phase Cut Output) (Max. 10A).
  • Aspirator Relay Output: 6 Stage (Phase Cut Output) (Max. 10A).
  • Heater Relay Output: 3 Stage (Direct Phase Output) (Max. 3A).
  • Damper Relay Output: 1 Stage (Dry Contact Output) (Max. 3A).

Physical Dimensions:

  • BCP-6-T (Room Panel): 85 mm (width) x 85 mm (height) x 14 mm (depth).
  • M1002 (Mainboard): 130 mm (width) x 105 mm (height) x 115 mm (mounting width).

Usage Features

The room panel provides intuitive control through several buttons:

  • On/Off Button: Toggles the device's power.
  • Mode Button: Cycles through operating modes: AUTO HEAT, AUTO FAN, MANUAL. Pressing for 2 seconds in ON mode accesses Weekly Program Settings.
  • Up Button: Increases the set temperature in automated mode or increases aspirator/ventilator/heater stage in manual mode. Used for adjusting values in settings menus.
  • Down Button: Decreases the set temperature in automated mode or decreases aspirator/ventilator/heater stage in manual mode. Used for adjusting values in settings menus.
  • Fan Button: Selects Aspirator, Ventilator, or Heater when the device is in manual mode. Used for confirming selections in settings menus. Pressing for 2 seconds in ON mode accesses Date & Time Settings.

Weekly Program Settings (BCP-6-T):

  • Allows users to set start and stop hours for each day.
  • Note 1: If the start hour is greater than the stop hour, the device will be off during the selected day.
  • Note 2: If start and stop hours are the same, the weekly program will not operate for that day.
  • Note 3: A "Timer On" logo indicates an active weekly program for the day.
  • Note 4: A "Timer Off" logo indicates an inactive weekly program for the day.

Date & Time Settings (BCP-6-T):

  • Allows setting the current hour, minute, day, month, and year.

Service Settings (Accessible by technical personnel):

  • Fan and Heater On/Off Time Settings: Adjusts delay times (5-30 seconds) for fan and heater operation.
  • Temperature Sensor Position Settings: Configures whether temperature control is based on the panel temperature (0) or return temperature (1).
  • Carbon Dioxide Settings: Enables (1) or disables (0) carbon dioxide mode.
  • Temperature Calibration: Allows calibration of the temperature sensor within a range of -9°C to +9°C.
  • Heater Stage Settings: Sets the maximum heater stage (0-3). If set to 0, the device operates only in Automatic Fan and Manual modes.
  • Backlight Settings: Configures backlight behavior: waits 5 seconds after button press (0), always off (1), or always on (2).
  • Factory Reset: Resets all settings to default values (Carbon Mode: Off, Control Temp: Panel, Delay Time: 10 seconds, Heater Stage: 3 Kademe, Device Mode: Automatic Heat, Set Temp: 23 °C).

Maintenance Features

  • Self-extinguishing plastic: The device is constructed with self-extinguishing plastic for enhanced safety.
  • Cleaning: The device should not be cleaned with corrosive cleaning materials or solvents (e.g., thinner, benzine, acid).
  • Installation Precautions:
    • The device should be mounted when there is no power.
    • It must be protected from vibration, humidity, and pollution.
    • Cross and shielded cables should be used for signal and communication lines to ensure reliable operation.
    • The control board should be mounted in a box away from direct sunlight and humidity.

Warning: Users are advised to read the manual and observe all cautions before installing the device. The responsibility for accidents and damages resulting from failure to follow warnings lies with the user. Any operation on the device that causes damage to the device or system will void the warranty. Settings menu changes should only be made by technical personnel.