Heat Controller, Inc. DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual
DXM2 OVERVIEW
The manufacturer’s next generation control board, DXM2,
is the geothermal industry’s rst two-way communication.
The DXM2 electronic control is a robust, microprocessor
based heat pump controller that is advanced and feature-
laden for maximum application exibility. The DXM2
Control has relay outputs for Compressor, Compressor
Speed, Reversing Valve, Alarm Relay, and 2 con gurable
relays for Fan, Fan Speed, HWG Pump, and Loop Pump,
and 2 con gurable accessory relay outputs. For on board
diagnostics, there are 2 LED’s to provide status indication.
There are inputs for safety pressure switches, low
temperature protection thermistors, condensate over ow
sensor, DIP switch selection inputs, thermostat inputs, night
setback inputs, and emergency shutdown input. Additional
con gurable temperature sensor inputs are available that
may be used for hot water, compressor discharge, leaving
air, leaving water, and entering water temperature sensors.
The DXM2 has an RS485 communications port to interface
with a communicating thermostat or other compatible
controls.
DXM2 Controller Part Number:
17B0002N02 DXM2 Control Board
General Operating Parameters
The following are general operating parameters for the
DXM2 Control:
Operating Environment: -40°F to 176°F and up to 95%
relative humidity, non-condensing.
Storage Environment: -40°F to 185°F and up to 95%
relative humidity, non-condensing.
Power Requirements
DXM2 only power draw -
Normally 8 VA draw at 24VAC
Maximum 12 VA draw at 24VAC. A dedicated 24VAC,
50-60Hz, 1Ph, 40VA transformer minimum is required for
typical WSHP application.
Relay and Connection Contact Ratings
The following relays are mounted on the DXM2 Control:
Compressor Relay: 40VA at 24VAC
Compressor Speed Relay: 28VA at 24VAC
Alarm Relay: 28VA at 24VAC
Reversing Valve: 28VA at 24VAC
Accessory Relay 1: 28VA at 24VAC
Accessory Relay 2: 28VA at 24VAC
Fan Enable / Loop Pump Relay: 1 HP at 240VAC
Fan Speed / HWG Pump Relay: 1 HP at 240VAC
Connection ratings on the DXM2 Control:
‘A’ terminal: 20VA at 24VAC. Larger solenoid valve draw
should be controlled with accessory relays.
Grounding
The control board must be grounded from one of the C
terminals.
Basic Control Features
Single or two–stage compressor control
Anti-short cycle protection
High pressure cut-out
Loss of charge cut-out
High and low voltage cut-outs
Water coil low temperature cut-out
Air coil low temperature cut-out
• Random start
Status LED and Fault LED
Reset lockout at unit or disconnect
• Condensate over ow sensor
Intelligent fault retry
• Test Mode
Multiple blower con guration options
Electric heat outputs
Accessory water valve connection
Advanced Control Features
Direct control of ECM blower
Intelligent hot water generator control
Two accessory relays con gurable for multiple
applications
Internal Flow Center output
Proportional valve output
Night setback with override capability
Emergency shutdown capability
Removable thermostat connector for ease of installation
and service
Accepts conventional heat pump (Y,O) or heat/cool (Y,W)
thermostat types
RS–485 port to interface with a communicating
thermostat or other compatible controls
Boilerless electric heat
• Con gurable inputs and outputs for advanced functions
DXM2 Electronic Heat Pump Controls