37


MODEL NUMBER
& HEATING
INPUT (BTUH)
MOTOR SWITCH
SETTINGS

EXTERNAL STATIC PRESSURE (IN.W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
    CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
GUH95C090C5XE
(90,000)
0 0 0 0 1,125
1,040
1 0 0 0 1,205
1,120
1,040
0 1 0 0 1,305
1,225
1,150
1,070
995
1 1 0 0 1,430
1,350
1,270
1,190
1,110
1,030
0 0 1 0 1,525 63 1,450 65 1,375
1,300
1,225
1,150
1,075
1,000
1 0 1 0 1,620 60 1,540 61 1,465 63 1,390 63 1,315 64 1,240
1,165
1,090
0 1 1 0 1,695 57 1,620 58 1,545 59 1,465 61 1,390 62 1,315
1,235
1,160
1 1 1 0 1,770 55 1,700 56 1,630 57 1,555 59 1,485 60 1,410 63 1,340 65 1,265
0 0 0 1 1,875 53 1,805 54 1,730 55 1,655 57 1,580 58 1,510 59 1,435 60 1,340 62
1 0 0 1 1,905 51 1,840 52 1,775 53 1,710 54 1,640 55 1,575 56 1,510 58 1,445 60
0 1 0 1 1,980 49 1,910 50 1,845 51 1,780 52 1,715 52 1,650 54 1,580 55 1,515 57
1 1 0 1 2,025 48 1,960 49 1,895 50 1,830 50 1,765 51 1,700 52 1,635 54 1,570 56
0 0 1 1 2,085 47 2,025 48 1,960 48 1,900 49 1,840 50 1,775 51 1,715 52 1,655 54
1 0 1 1 2,135 46 2,070 46 2,010 47 1,945 48 1,880 49 1,815 50 1,750 51 1,685 53
0 1 1 1 2,200 44 2,145 45 2,090 45 2,035 46 1,980 47 1,925 48 1,870 49 1,820 51
1 1 1 1 2,280 42 2,225 43 2,170 44 2,115 45 2,065 46 2,010 47 1,955 48 1,900 49
GUH95C108D5X
E
(108,000)
0 0 0 0 1,395 62 1,350 64 1,305 66 1,260 68 1,210
1,165
1,120
1 0 0 0 1,465 58 1,420 60 1,375 62 1,330 64 1,290
1,245
1,200
1,155
0 1 0 0 1,555 57 1,510 59 1,470 61 1,425 63 1,380
1,340
1,295
1,250
1 1 0 0 1,625 54 1,585 56 1,540 58 1,500 59 1,460
1,415
1,375
1,335
0 0 1 0 1,690 53 1,650 55 1,610 56 1,570 58 1,530
1,485
1,445
1,405
1 0 1 0 1,760 51 1,715 52 1,670 54 1,625 56 1,575 64 1,530
1,485
1,440
0 1 1 0 1,835 50 1,790 52 1,745 54 1,695 56 1,650 62 1,605
1,555
1,510
1 1 1 0 1,885 49 1,840 50 1,790 52 1,745 53 1,700 60 1,655 63 1,610 65 1,565
0 0 0 1 1,945 49 1,900 51 1,850 52 1,805 53 1,760 58 1,710 59 1,665 60 1,620 62
1 0 0 1 1,950 47 1,905 49 1,860 50 1,820 51 1,775 55 1,735 56 1,690 58 1,650 60
0 1 0 1 2,075 47 2,030 49 1,990 50 1,945 51 1,900 52 1,855 54 1,810 55 1,770 57
1 1 0 1 2,125 45 2,085 47 2,040 49 2,000 50 1,955 51 1,910 52 1,870 54 1,825 56
0 0 1 1 2,170 45 2,130 47 2,090 48 2,045 49 2,005 50 1,965 51 1,925 52 1,880 54
1 0 1 1 2,215 44 2,180 45 2,140 47 2,105 48 2,070 49 2,035 50 2,000 51 1,965 53
0 1 1 1
2,225 47 2,165 48 2,100 49 2,040 51
1 1 1 1
2,170 47 2,120 48 2,065 49
GUH95C120D5X
E
(120,000)
0 0 0 0 1,395 69 1,350 68 1,305
1,260
1,210
1,165
1,120
1 0 0 0 1,465 66 1,420 66 1,375
1,330
1,290
1,245
1,200
1,155
0 1 0 0 1,555 62 1,510 64 1,470 69 1,425
1,380
1,340
1,295
1,250
1 1 0 0 1,625 61 1,585 62 1,540 67 1,500 69 1,460
1,415
1,375
1,335
0 0 1 0 1,690 59 1,650 60 1,610 64 1,570 66 1,530 68 1,485 70 1,445
1,405
1 0 1 0 1,760 58 1,715 59 1,670 63 1,625 64 1,575 66 1,530 68 1,485 70 1,440
0 1 1 0 1,835 57 1,790 59 1,745 61 1,695 63 1,650 64 1,605 66 1,555 68 1,510 70
1 1 1 0 1,885 57 1,840 58 1,790 60 1,745 62 1,700 63 1,655 65 1,610 66 1,565 69
0 0 0 1 1,945 57 1,900 56 1,850 59 1,805 61 1,760 62 1,710 63 1,665 64 1,620 67
1 0 0 1 1,950 55 1,905 55 1,860 58 1,820 59 1,775 61 1,735 62 1,690 63 1,650 65
0 1 0 1 2,075 53 2,030 54 1,990 56 1,945 58 1,900 59 1,855 60 1,810 61 1,770 63
1 1 0 1 2,125 52 2,085 53 2,040 55 2,000 56 1,955 58 1,910 59 1,870 60 1,825 62
0 0 1 1 2,170 51 2,130 52 2,090 54 2,045 55 2,005 56 1,965 58 1,925 59 1,880 60
1 0 1 1 2,215 51 2,180 51 2,140 53 2,105 54 2,070 55 2,035 56 2,000 58 1,965 59
0 1 1 1
2,225 54 2,165 55 2,100 56 2,040 58
1 1 1 1
2,170 54 2,120 55 2,065 57
NOTES:
1 Motor Switch Settings are for heating speeds using HEAT switches 1,2,3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8
2 Two openings are required for airflows above 1,600 CFM if the filter(s) is (are) adjacent to the furnace
3 Data is shown without filter
4.Temperature rises in the table are approximate. Actual temperature rises may vary
5.Cells shaded in gray indicate a temperature rise outside of the recommended range.
6 When in low stage,the circulating airflow is 70% of the tables high value (2-stage furnaces only).
