HEAT-FLO INDIRECT-FIRED WATER HEATERS
MODELS 30, 40, 40L, 50, 60, 60L, 80, 115
AND 60-HO, 80-HO, 80-HO-C, 115-HO, 115-HO-C
85-XHO, 115-XHO HIGH OUTPUT UNITS
FOR SINGLE WATER HEATER INSTALLATIONS
Heat-Flo, Inc.
15 Megan Ct., P.O. Box 612 Uxbridge, MA 01569 USA
Bulletin I0-010115
For service or repairs to the water heater, call your heang contractor. Your water heater has been manufactured
to provide years of service. In order to insure proper service, the following informaon is provided to assist
in enabling the installaon, operaon, and maintenance of this water heater. For your comfort, safety, and
convenience, we recommend that this water heater be installed and serviced by a plumbing professional. When
the installaon is completed, keep this manual with the water heater. Informaon and specicaons outlined
in this manual in eect at the me of prinng of this manual. Heat-Flo reserves the right to disconnue, change
specicaons, or change system design at any me without noce.
Conforms to UL STD 174 and NSF/ANSI 372
Cered to CAN/CSA STD C22.2 No. 110-94
INSTALLATION, OPERATING, AND
SERVICE INSTRUCTIONS

Questions and Answers

  • B
    Breanna TurnerAug 12, 2025
    How to fix no hot water in my Heat-Flo HF-30?
    • M
      Michael BrownAug 12, 2025
      If you have no hot water at the faucets with your Heat-Flo Water Heater, several factors could be the cause. The boiler or circulator might not be operating, or the thermostat setting could be incorrect. A zone valve may not be opening, or there could be an electrical issue, sediment/scale buildup, or a clogged filter. Try pressing the reset button, checking the main cut-off switch, fuses/breakers, and power supply. Also, verify the shaft coupling and thermostat setting. If the boiler, circulator, and thermostat are working, but the boiler cycles on the high limit before the tank thermostat is satisfied, the coil may need chemical cleaning. Finally, inspect and clean or replace the filter.
  • N
    Nathan AllenAug 20, 2025
    What to do if my Heat-Flo Water Heater runs out of hot water?
    • A
      andrew65Aug 20, 2025
      If your Heat-Flo Water Heater runs out of hot water quickly, the thermostat setting might be too low, or the boiler could be undersized without priority for domestic water heating. The peak hot water draw might exceed the tank's storage capacity, or there could be sediment/scale buildup, or a faulty thermostat. Try turning the thermostat to a higher setting or rewiring for priority. Compare peak usage to the tank volume. Clean the coil or replace the thermostat.
  • S
    Sonia CummingsAug 31, 2025
    Why is the water from my Heat-Flo HF-30 too hot?
    • C
      Christina SmithAug 31, 2025
      If the water from your Heat-Flo Water Heater is too hot, the thermostat may be set too high, or there could be improper system plumbing or wiring. Try lowering the thermostat setting. Compare the plumbing and wiring to the installation guide and inspect the check valves.

Heat-Flo HF-30 Specifications

General IconGeneral
CategoryWater Heater
ModelHF-30
TypeIndirect Water Heater
Capacity30 gallons
Tank Capacity30 gallons
Heat ExchangerCopper
Diameter22 inches
Maximum Working Pressure150 PSI
Test Pressure300 PSI
MaterialSteel
Tank MaterialSteel
Primary Loop Connection Size1 inch NPT
Domestic Water Connection Size3/4 inch
Insulation2" foam insulation
Energy SourceIndirect (from boiler)