Why does my Hegwein ZT0 Burner shut down during operation?
- LLynn BrownAug 9, 2025
If the Hegwein Burner experiences fault shutdowns during operation, it could be due to fluctuating combustion chamber or supply pressure levels, which results in flame blow-off. Check the pressure settings at the test nipples and, if necessary, provide a differential pressure regulation system for gas and air. Another cause could be that the pilot flame is highly subject to influence by the main flame or is suffocated; in this case, change the position of the gas fired igniter. You may need to use a more powerful gas fired igniter.