No. Description Setting
090
Signalling of switching output
Signalises the control of switching outputs by a
flashing heating resp. cooling symbol.
0 = deactivated
1 = activated
Standard: 1
110
Control direction switching output
Sets the control direction of connected actua-
tors:
• Normally closed (NC)
• Normally open (NO)
0 = NC
1 = NO
Standard: 0
161
Antifreeze temperature
Activates the antifreeze protection function
when the temperature falls below the set tem-
perature.
5 ... 10 °C
Standard: 5
170
Smart Start/Smart Stop function
CU-REGC-V CUREGCV)
Teaches the temperature behaviour of the room.
0 = deactivated
1 = activated
Standard 1
190
Valve protection function
Cyclic opening of the valve in order to avoid clog-
ging.
0 ... 28 days
Standard: 14
191
Valve activation duration
Time for triggering actuators for performing the
valve protection function.
0 ... 10 minutes
Standard: 5 min
Service menu