EasyManua.ls Logo

Herrmidifier 6000 Series - Key Features

Herrmidifier 6000 Series
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Key Features
Adjustable Setpoints
Capacity
Range = 50-100%
Preset at 100% for 6000-1,3,4
Preset at 50% for 6000-2
Low Drain Threshold
Range = 50-100%
Preset at 90%
Cycle Time
Range = 60-300 seconds
Preset at 60 seconds
Faults
Overcurrent
138% of Rated Current
System Shutdown
Fill System
Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
System Shutdown
End of Cylinder Life
6 hours of operation while on cylinder full without achieving capacity setpoint
System Shutdown (See Pg. 14 for Manual Override)
Conductivity*
Micromhos
(approx.)
Average Life**
Expectancy – Hrs.
(approx.)
100 2000
135 1900
170 1800
250 1300
500 800
750 650
1000 500
*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board
adjustments and replacement tank information (GT-176-1).
Unit performance may be affected.
Operation on water of less than 60 micromho is not recommended.
**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.
5

Related product manuals