(1) The unit of measurement depends on P2 parameter
(3) Properly set the parameters corresponding to the regulators after modifying P2 parameter
(4) The parameter has effect even after an interruption in the power supply that occurs while the instrument in switched on
(5) The time established with the parameter is counted even when the instrument is switch off
(6) If parameter C1 is set to 0, the delay after the end of the cell probe error will be 2 minutes
(7) The parameter differential is 2,0 °C / 4 °F
(8) If when the instrument is switched on the condenser temperature is already above that established in C7 parameter, than C8 parameter will not have effect
(9) The instrument stores the defroster interval count every 30 minutes; the modifcation of d0 parameter takes effect following the end of the preceeding interval of following
the activation of manual defrosting
(10) The display returns to normal operation when, at the end of evaporator fan disactivation, the cell temperature falls below that at which the display was initially blocked
(or if a temperature alarm is signaled)
(11) If P3 parameter is set 0 or 2, the instrument will function as if d8 parameter were set to 0
(12) If when defrosting is activated, the operating duration of the compressor is less than the time established with parameter dA, the compressor will remain on for the
amount of time necessary to complete defrosting
(13) If P3 parameter is set to 0, the instrument will function as if A0 parameter were set to 0, but will not store the alarm
(14) During defrosting and dripping and when the evaporator fan is stopped, the temperature alarms are absent, provided that these where signaled after the activation of
defrosting
(15) During activation of the door microswitch input, the maximum temperature alarm is absent, provided the alarm was signaled after the activation of the input
(16) When power is restored, the alarm will always be signaled
(17) If P3 parameter is set to 0, the instrument will function as if F0 parameter were set to 2
(18) The parameter is also modified pressing for some seconds button UP on the keyboard
(19) If parameter P4 is set to 0, the condenser fan will work together with the compressor
(20) The compressor is switched off 10 seconds after the activation of the input; if the input is activated during defrosting or when the evaporator fan is disactiveted, the
activation will not have any effect on the compressor
(21) The instrument stores the alarm once the time established in i2 parameter has expired; if i2 parameter is set to -1, the instrument will not store the alarm
(22) Make sure that the time established with i7 parameter is less than that established with i9 parameter
(23) To avoid damaging the unit connected to the instrument, change the parameter setting when the instrument is switched off
(24) If u2=0, switching off the instrument will cause the cell light or the aux output to switch off (the next time the instrument is switched on the unit connected will remain
switched off); If u2= 1, switching off the instrument will not cause the cell light or the aux output to switch off (the next time the instrument is switched on the unit connected
will remain switched on)