1.3 Specifications H 7033
Three-Wire Transmitter Supply
Supply voltage (L+)
regulated
24...30 VDC, PELV, SELV
Class 2
Current consumption max. 4 A
Transmitter supply (three-wire transmitter)
Transmitter supply U
T
Voltage between S and INT
Current (transmitter supply) max. 500 mA
Transmitter supply voltage monitoring.
Observe the minimum transmitter supply voltage
U
Tmin
of the connected transmitter!
Monitoring of the transmitter supply voltage (SM)
Monitored transmitter supply voltage
U
TM
U
TM
= U
Tmin
+ I
T
x R
wire
+ U
Fuse 500 mA
+ Tolerance
Fuse
G-fuse cartridge 500 mA Part no. 57 0174059
Filter
Time constant τ
τ = 8 ms
Filter impedance 400
Mounting H 7033
Mounting On DIN rail 35 mm
Mounting position
Horizontally or vertically, no mounting distance
required
Special mounting conditions for
USA/Canada
Mount in Type 3 control cabinet or in
Type 3 assembly housing
General
Type of protection IP20
Weight approx. 220 g
Operating temperature 0...+60 °C
Storage temperature -40...+85 °C
Dimensions (H x W x D) approx. 112 x 125 x 40 mm
Table 3: Specifications