What does it mean when my Himel Water Pump drive shows module protection?
- DdiazchristopherSep 2, 2025
If your Himel Water Pump drive shows module protection, it can be triggered by several issues. It may be due to instantaneous overcurrent of drive, in that case see overcurrent countermeasures. Check the wiring, as the output three phases may have a phase-to-phase short circuit or grounded short circuit and rewiring may be required. Blocked air duct or damaged fan can cause this, so clear the air duct or replace the fan. If the ambient temperature is too high, reduce it. Loose wire connection or plug-in of control board can be the cause, so check and reconnect the wire. Also, check wiring for an abnormal current waveform caused by output phase loss. Finally, if the auxiliary power supply is damaged, or there is undervoltage of drive, seek for service.