different units.
Address
Name Description R/W
(note 1)
0 EXIST
0: Not exist
R
1: Exist
1 SYSTEM_ADDRESS H-LINK 1: 0~15 R
2 UNIT_ADDRESS H-LINK 2: 0~63 R
3 SET_ONOFF
ON/OFF setting order:
R/W0: Stop
1: Run
4 SET_MODE
Mode setting order:
R/W
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
5 SET_FAN
Fan setting order:
R/W
0: Low
1: Medium
2: High
6 SET_TSET
Setting temperature
R/W
17ºC ~ 30ºC
7 6(7B/289(5
Louver setting
R/W
0 ~ 7 (7 is Auto)
8 SET_CENTRAL
Central Setting:
R/W
Bit 0: ON/OFF (always can be stopped)
Bit 1: Mode
Bit 2: Setting temperature
Bit 3: Fan
Bit 4: Louver
9 READ_ONOFF
ON/OFF read:
R0: OFF
1: ON
10 READ_MODE
Mode read:
R
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
11 READ_FAN
Fan read
R
0: Low
1: Medium
2: High
12 READ_TSET
Setting temperature read
R
(17ºC to 30ºC)
13 5($'B/289(5
Louver read
R
0 ~ 7 (7 is Auto)
14 RCS_GROUP
Remote controller group
R
0 ~ 255
15 TIN Inlet temperature (Note 2) R
16 TOUT Outlet temperature (Note 2) R
2SHUDWLRQDQGFRQ¿JXUDWLRQRISDFNDJHGXQLWV
PMML0409A rev.1 - 10/201650