Name Description R/W
(note 1)
17 TGAS Gas pipe temperature (Note 2) R
18 TLIQUID Liquid pipe temperature (Note 2) R
19 ERROR_CODE Alarm code R
20 STOP_CAUSE Compressor stop cause R
21 9$/9(B23(1 Indoor unit expansion valve opening R
22 OPER_CONDITION
Unit operation condition
R
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
23 DEFROS Defrost R
24 AMBIENT_TEM Ambient temperature (Note 2) R
25 RCS_TEMP
Remote control switch temperature
R
(Only when available in unit) (Note 2)
26 TIMER_DISABLED
Timer disabled
R/W0: Enabled
1: Disabled
27 OPTIONS Options setting (Note 6) R
28 POWER Calculated power consumption (Note 5) R
29 COMP_QTY Running compressor quantity (Note 3) R
30 COMP_FREQ Inverter compressor frequency R
31 REM_TEMP
Remote sensor temperature
R
(Only when accessory is installed) (Note 2)
N O T E
1 2IIVHWSRVLWLRQLV1$GGUHVVDVVKRZQLQWDEOHZKHUH1LVXQLWDGGUHVV8QLWDGGUHVVDVVHWLQ&61(70DQDJHU%06
FRQ¿JXUDWLRQGLDORJXH%HFDUHIXOEHFDXVHZHDUHXVLQJDGGUHVVDV¿UVWUHJLVWHUDQGLQ0REGXVFRXOGEHXVHGQXPEHUDV¿UVWYDOXH,QWKDW
FDVHLWZLOOEHQHFHVVDU\WRDGGWRWKHDGGUHVVFDOFXODWLRQ
2 These numbers refer to signed 16-bit value using 2-complement format for negative values.
3 5XQQLQJFRPSUHVVRUTXDQWLW\LVRQO\YDOLGIRUXQLWVZLWKPRUHWKDQRQHFRPSUHVVRU,QFDVHRILQYHUWHUYDOXHVKRZHGLV
4 2SWLRQVVHWWLQJJLYHDOZD\V
5 Indoor unit consumption percentage in relation to all the installation power consumption
2SHUDWLRQDQGFRQ¿JXUDWLRQRISDFNDJHGXQLWV
PMML0409A rev.1 - 10/201651