Transport the product as close to the installation location as practical before unpacking.
Do not put any material on the product during transportation.
Confirm the number of parts by referring to the model printed on the package before unpacking.
Check that no foreign materials are inside the parts before fixing work.
Cut the end of the pipe to meet with the specified pipe size as shown in the figures.
Locate branch pipes on the same horizontal plane with minimum straight length after vertical bend.
Secure pipe ends with caps when passing through walls and avoid direct ground contact.
Ensure stop valves are closed and blow pipes with nitrogen when brazing.
Check for refrigerant leakage and attach insulation to all branches and field piping.
Connect liquid piping with 9.53mm size for units 2HP or smaller and piping over 15 meters.
Perform insulation when piping temperature decreases and cap open ends to prevent moisture intrusion.
This document is an installation manual for Hitachi Multi-Kits, specifically for models E-102SN, E-162SN, E-242SN, and E-302SN. It provides essential information for the proper installation and handling of these kits, which are designed for R410A SET-FREE series outdoor units.
The Multi-Kits serve as multiple pipe connecting kits, facilitating the connection of refrigerant piping between outdoor units and indoor units in R410A SET-FREE series air conditioning systems. They include various components such as branch pipes for both gas and liquid lines, insulation for these lines, reducers for gas lines, expanders for liquid lines, and tape for securing insulation. The manual details the correct procedures for piping connection, including specific pipe sizes and installation positions, to ensure optimal system performance and safety.
Models Covered:
Applicable Outdoor Units:
Piping Connection Sizes (End of Multi-Kits): The manual provides detailed diagrams for each model (E-102SN, E-162SN, E-242SN, E-302SN) illustrating the finished pipe end sizes for both gas and liquid lines. These diagrams show various inner diameters (ID) and outer diameters (OD) at different points of the branch pipes, indicating where cuts should be made to match the connecting pipe sizes.
Air Tight Test Pressure:
Recommended Insulation Thickness:
Piping Size for Liquid Piping (2HP or smaller units, piping length 15m or longer):
Minimum Depth for Brazing (B):
Installation Position:
Piping Connection:
Safety Precautions:
The manual primarily focuses on installation and does not detail specific maintenance features for the Multi-Kits themselves. However, it emphasizes proper installation practices that contribute to the long-term reliability and performance of the overall air conditioning system, thereby reducing the need for corrective maintenance.
Key points related to system integrity and longevity:
Post-Installation Recommendation: