Items Optional Function Individual setting Setting condition Contents
EE Automatic fan speed control
00
01
Not available
Available
F0 Not prepared - - Not used
F1
Automatic OFF timer setting
* Do not set the functions “0C”~“0F” when
2 (two) remote control switches are used
in the same remote control group.
×
00
01
02
23
24
0A
0B
0C
0D
0E
0F
No function
OFF Timer by 1 hr
OFF Timer by 2 hrs
OFF Timer by 23 hrs
OFF Timer by 24 hrs
OFF Timer by 30 min.
OFF Timer by 90 min.
OFF Timer by 40 min.
OFF Timer by 45 min.
OFF Timer by 50 min.
OFF Timer by 55 min.
F2 Remote control main-sub setting ×
00
01
Main
Sub
F3 Automatic reset of setting temperature (*4) ×
00
01
(*10)
Not available
Available
F4 Automatic reset time ×
00
01
02
03
(*10)
30 min.
15 min.
60 min.
90 min.
F5
Automatic reset temperature for cooling
(*5)
×
19
20
25
29
30
19
o
C
20
o
C
25
o
C (Factory setting)
29
o
C
30
o
C
F6
Automatic reset temperature for heating
(*6)
×
17
18
21
29
30
17
o
C
18
o
C
21
o
C (Factory setting)
29
o
C
30
o
C
F7
Operation stoppage prevention by remote
control switch operational error (*7)
×
00
01
Not available
Available
F8 Lock function for operation mode selection ×
00
01
Not available
Available (Factory setting)
F9 Lock function for temperature setting ×
00
01
Not available
Available (Factory setting)
FA Lock function for fan speed selection ×
00
01
Not available
Available (Factory setting)
Fb Lock function for swing louver operation ×
00
01
Not available
Available (Factory setting)
FC
Cooling lower limit for setting temperature
(*5)
×
00
01
02
09
10
Standard
Lower limit +1ºC
Lower limit +2ºC
Lower Limit +9ºC
Lower Limit +10ºC
Fd
Heating upper limit for setting temperature
(*6)
×
00
01
02
11
12
Standard
Upper limit –1
o
C
Upper limit –2
o
C
Upper limit –11
o
C
Upper limit –12
o
C
FUNCTION SELECTION AND SETTING