(4) Setting Refrigerant Cycle No.
In the same refrigerant cycle, set the same refrigerant cycle No. for the outdoor unit and the indoor units
as shown below. The range of refrigerant cycle No. is between 0 and 63.
Refrigerant Cycle No. = The value of the DSW4 (System Address Setting: Double Digit) + The value of the
RSW1(System Address Setting: Single Digit).
DSW4 (System Address Setting: Double Digit) RSW1 (System Address Setting: Single Digit)
DIP Switch Setting Value DIP Switch Setting Value
0 0
10 1
20 2
30 3
40 4
50 5
60 6
7
8
9