– 6 –
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2,300mm or more
Maximum pipe length 15m
Minimum pipe length 5m
above 200mm
above 700mm
above 200mm
above 50mm when
installed on the
ceiling of balcony
(
)
above 100mm
above 100mm
give clearance as
wide as possible
Plug
Figure showing the installation of Indoor anf Outdoor unit
The installation height of indoor unit must be 2.3m or more.
CAUTION
!
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products).
inner diameter ø 16mm
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
The difference in height
between the indoor and
outdoor unit should be
kept max 10m.
The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then warapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).