• Inaddition,asetofcalibratedweighingscalesshallbeavailableandingoodworkingorder.
• Hosesshallbecompletewithleak-freedisconnectcouplingsandingoodcondition.
• Beforeusingtherecoverymachine,checkthatitisinsatisfactoryworkingorder,hasbeenproperlymaintainedandthat
any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
• Consult manufacturer if in doubt.
• The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant
Waste Transfer Note arranged.
• Donotmixrefrigerantsinrecoveryunitsandespeciallynotincylinders.
• If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to
makecertainthatammablerefrigerantdoesnotremainwithinthelubricant.
• The evacuation process shall be carried out prior to returning the compressor to the suppliers.
• Only electric heating to the compressor body shall be employed to accelerate this process.
• When oil is drained from a system, it shall be carried out safely.
• Applianceshallbeinstalled,operatedandstoredinaroomwithaoorarealargerthanX(forX,seeindoorunit
instructionmanual).
• Theinstallationofpipe-workshallbekepttoaaroomwithaoorarealargerthanX(forX,seeindoorunitinstruction
manual).
• Thepipe-workshallbecompliantwithnationalgasregulations.
• ThemaximumrefrigerantchargeamountisXkg(Xseebelow).
• Whenmovingorrelocatingtheairconditioner,consultexperiencedservicetechniciansfordisconnectionand
reinstallation of the unit.
• Do not place any other electrical products or household belongings under indoor unit or outdoor unit.
• Condensation dripping from the unit might get them wet, and may cause damage or malfunction of your property.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• Theapplianceshallbestoredinaroomwithoutcontinuouslyoperatingignitionsources(forexample:openames,an
operatinggasapplianceoranoperatingelectricheater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• Tokeepventilationopeningsclearofobstruction.
• Theapplianceshallbestoredinawell-ventilatedareawheretheroomsizecorrespondstotheroomareaasspeciedfor
operation.
• Theapplianceshallbestoredinaroomwithoutcontinuouslyoperatingopenames(forexampleanoperatingappliance)
andignitionsources(forexampleanoperatingelectricheater).
• Anypersonwhoisinvolvedwithworkingonordismantelingarefrigerantcircuitshouldholdacurrentvalidcerticate
fromanindustry-accreditedassessmentauthority,whichauthorisestheircompetencetohandlerefrigerantssafelyin
accordancewithanindustryrecognisedassessmentspecication.
• Servicing shall only be performed as recommended by the equipment manufacturer.
• Maintenanceandrepairrequiringtheassistanceofotherskilledpersonnelshallbecarriedoutunderthesupervisionof
thepersoncompetentintheuseofammablerefrigerants.
• The appliance shall be installed and stored so as to prevent mechanical damage from occurring.
• MechanicalconnectorsusedindoorsshallcomplywithISO14903.Whenmechanicalconnectorsarereusedindoors,
sealingpartsshallberenewed.Whenaredjointsarereusedindoors,thearepartshallbere-fabricated.
• Theinstallationofpipe-workshallbekepttoaminimum.
• Mechanical connections shall be accessible for maintenance purposes.
Max. Refrigerant Charge Amount X (kg)
Model 3.0HP 3.5HP 4.0HP 5.0HP 6.0HP 6.5HP
Max.RefrigerantCharge 2.1 2.71 3.26 3.76 4.26 4.66