Electrical wiring diagram
Model (capacity) Power supply
ELB
Power source
cable size
Transmission
cable size
Circuit breaker
(A)
Rated current (A)
Nominal sensitive
current (mA)
EN60335-1*1 EN60335-1*1
3.0/3.5HP 220-240V~,50Hz 25 30 3x2.5mm
2
4x1.5mm
2
25
4.0HP 220-240V~,50Hz 40 30 3x4.0mm
2
4x1.5mm
2
40
5.0/6.0/6.5HP 380-415V3N~,50Hz 32 30 5x2.5mm
2
4x1.5mm
2
32
Max. Running Current (A): REFER TO NAMEPLATE
NOTE:
1 Followlocalcodesandregulationswhenselectingeldwires,andalltheabovearetheminimumwiresize.
2 Usethewireswhicharenotlighterthantheordinarypolychloroprenesheathedexiblecord.(CorddesignationH07RN-F).
3 Thewiresizesmarkedwith*1intheabovetableareselectedatthemaximumcurrentoftheunitaccordingtotheEuropean
Standard,EN60335-1.
4 Whentransmissioncablelengthismorethan15meters,alargerwiresizeshouldbeselected.
5 InstallmainswitchandELBforeachsystemseparately.SelectthehighresponsetypeELBthatisactedwithin0.1second.
6 Inthecasethatpowercablesareconnectedinseries,addeachunitmaximumcurrentandselectwiresbelow.
Selection According to EN60335-1
Current i (A) Wire Size (mm
2
)
i≤6 0.75
6<i≤10 1
10<i≤16 1.5
16<i≤25 2.5
25<i≤32 4
32<i≤40 6
40<i≤63 10
63<i *2
*2:Inthecasethatcurrentexceeds63A,donotconnectcablesinseries.
<Attentions when Connecting the Power Supply Wiring>
1 Whenconnectingtheterminalblockusingstranded
wire,makesuretousetheroundcrimp-styleterminalfor
connectiontothepowersupplyterminalblock.Placethe
round crimp-style terminals on the wires up to the covered
part and secure them in place.
2 Whenconnectingtheterminalblockusingasinglecorewire,
be sure to perform curing.
Single core wire
Terminal
Stranded wire
Covered part
Roundcrimp-
style terminal
INSTALLATIONINSTRUCTIONS
HO2019292HA