Single Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between
O.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
*1 *2 *3 *4 *5 *6 *7 *8 *9 *10 *11 *12 *14 *15 *17
RAS-3HVRNM2
32 5 32 40 5 40 32 5 32 4 0.75 4 0.75 0.75 2.0
RAS-4HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 3.5
RAS-5HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 3.5
RAS-6HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 3.5
RAS-7HVRNM2
50 10 40 60 10 50 50 10 40 10 0.75 6 0.75 0.75 3.5
Twin Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1 *2 *3 *4 *5 *6 *7 *8 *9 *10 *11 *12 *14 *15 *16 *17
RAS-3HVRNM2
32 5 32 40 5 40 32 5 32 4 0.75 4 0.75 0.75 0.75 2.0
RAS-4HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-5HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-6HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
Triple Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1 *2 *3 *4 *5 *6 *7 *8 *9 *10 *11 *12 *14 *15 *16 *17
RAS-4HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-5HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-6HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
Quad Type
Term
(measure)
Model
ELB
(A)
Normal Current
of Main Switch
(A)
Fuse Capacity
of Main Switch
(A)
Wiring Capacity (mm
2
)
Power Supply
Between O.U. and I.U.
Between I.U. and I.U.
Earth
Wiring
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
CASE A
CASE B
Indoor
CASE B
Outdoor
Power
Source
Cable
Control
Cable
Power
Source
Cable
*1 *2 *3 *4 *5 *6 *7 *8 *9 *10 *11 *12 *14 *15 *16 *17
RAS-4HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-5HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
RAS-6HVRNM2
50 5 40 60 5 50 50 5 40 10 0.75 6 0.75 0.75 0.75 3.5
ELB: Earth Leakage Breaker
I.U.: Indoor Unit
O.U.: Outdoor Unit
Table 7.2 Recommended Wiring Capacity and Size