Basic Heating Operation
Notes:
(1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or “Auto mode” and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor speed (calculated value in Table 3) larger than WMAX.
(2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off.
(3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal heating mode, compressor maximum speed WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if outdoor temperature
is lower than 4°C.
(6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 0.5 seconds “ON” and 0.5 second “OFF”.
(7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C.
(8) When fan is set to
compressor speed will be limited to WSZMAX.
“Lo”, compressor speed will be limited to WBEMAX. When fan is set to "Med", compressor speed will be limited to WJKMAX. When fan is set to “Silent”,
(9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode.
(10) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor speed is actual speed x DWNRATEW.
Table 3 Compressor speed
Notes:
1. See the data in Table 1-Table 2 on
page 47 & 49 for each constant in
capital letters in the diagrams.
Temperature
difference
(with shift value)
Calculated
compressor speed
1.66°C
2200 min
–1
2.00°C
2600 min
–1
2.33°C
3000 min
–1
2.66°C
3.00°C
3400 min
–1
3500 min
–1
E08H2A E10H2A
3.33°C
3500 min
–1
3.66°C
3500 min
–1
2200 min
–1
2600 min
–1
3000 min
–1
3400 min
–1
3800 min
–1
4200 min
–1
4400 min
–1
1.33
0.66
10sec.
60sec.
WMAX2
Hi
Lo
15sec.
15sec.
15sec.
Lo Lo Lo
15sec. 15sec.
3min.
Lo
3000
SFTDSW
WMIN
Indoor fan
Operarion lamp
Ultra-Hi
Hi
Med
Lo
Silent
Ultra-Lo
Max.
Rating
Min.
Outdoor fan
Start/Stop button
Thermo judgment
Defrost signal
Preheating judgment
Heating set temperature
(remote control set temperature
(+))
Fan speed set to "auto"
Start
Max.3 min.
Preheating released
Preheating released
Control by heat exchanger temperature
Control by heat exchanger temperature
Control by
heat exchanger temperature
Control by
heat exchanger temperature
Control by
heat exchanger temperature
Thermo OFF
Thermo
OFF
Thermo
OFF
Stop
Start
Stop
Start
Stop
Compressor speed
Dashed period
td
20min.
Reversing valve
(Cooling "ON" mode)