2. Indoor fan does not operate (others are normal)
Can the fan be stopped by remote 
control?
The microcomputer fan PWM 
 
Replace the microcomputer
.
Replace the fan motor
.
Replace the microcomputer
.
Perform final operation check.
Are pulse signals output at 
microcomputer pins  15 - 18  when 
auto swing is turned on in the fan 
mode?
Replace the microcomputer.
Is a voltage over 15 or below 10V 
being generated on the 12V line?
No
No
No
No
Perform final operation check.
output (at pin  
24
 ) is 1 - 5V. 
Check IC711. If it is normal, 
replace the air deflector motor.
Replace IC111.
3. Air deflector does not move (others are normal)
YesYes
Yes
Yes
4. Check the control P.W.B. (power circuit)
Is 35V or 20V being output 
at pin  5  relative to 0V at
pin  3  of CN3? 
Is 12V or 7V being output 
at (+) relative to 0V at (-) of 
C114? 
Is ICP1 normal?
Normal if it is less than 1 .
Blown (open) if it is 1 or more.
Replace ICP1. Check if the air 
deflector motor is shorted, and 
IC111, Q111, C114, ZD121 are 
defective.
If shorted / defective, ICP1 will be 
open again.
Replace the terminal board.
Insert the connection cable 
securely.
Replace IC121. Check if a short 
occurs in the 5V line.
If the 5V line is shorted, ICP1 will 
be open again.
Check to see if the connection cables are 
disconnected or reversed.
If normal, check the outdoor unit P.
W.B. 
Has the terminal board 
thermal fuse blown (open)?
Replace Q111 and IC111
.
Is DC5V being generated?
Perform final operation check.
: When the unit is not in operation, the voltage across the 35V line may drop to 20V
.
: When the unit is not in operation, the voltage across the 12 V line may drop to 7V
.
1
Yes
Ye
s
(Normal)
Yes
(Open)
Yes
No
No
No
Ye
s
No
No
2
2
1