14 REFRIGERANT PIPING
Before refrigerant piping work, drain piping work and insulation
are required. Refer to the 'UDLQSLSLQJ for details.
D A N G E R
• Do not perform refrigerant piping work, drain pumping, and
refrigerant charge without referring to Installation and Operation
Manual of the outdoor unit.
• 8VH WKH VSHFL¿HG QRQÀDPPDEOH UHIULJHUDQW 5$ WR WKH
outdoor unit in the refrigerant cycle. Do not charge the unit with
PDWHULDO RWKHU WKDQ 5$ VXFK DV K\GURFDUERQ UHIULJHUDQWV
SURSDQHRUHWFR[\JHQÀDPPDEOHJDVHVDFHW\OHQHRUHWFRU
poisonous gases when installing, maintaining and moving the
XQLW7KHVHÀDPPDEOHVDUHH[WUHPHO\GDQJHURXVDQGPD\FDXVH
DQH[SORVLRQD¿UHDQGLQMXU\
14.1 PIPING POSITION
177
140
180
145
94
Wiring connection
Drain pipe
connection
Refrigerant liquid pipe
connection
Refrigerant gas pipe
connection
(Drain pipe)
(Drain pipe)
(Gas pipe)
(Liquid pipe)
(Gas pipe)
(Liquid pipe)
14.2 PIPING CONNECTION SIZE
1 Prepare locally-supplied copper pipes.
2 Select the appropriate pipe size according to the table
below:
mm (in.)
Model Gas Pipe Liquid Pipe
RCIM-0.6FSN4
RCIM-0.8FSN4
RCIM-1.0FSN4
RCIM-1.5FSN4
RCIM-2.0FSN4
Ø12.7 (1/2) Ø6.35 (1/4)
RCIM-2.5FSN4 Ø15.88 (5/8) Ø9.52 (3/8)
3 Select clean copper pipes. Make sure there is no dust and
water inside. Use a pipe cutter when cutting the pipes, to
avoid a grind swarf generation. Do not use a saw or a grind
stone to cut pipes. Blow the inside of the pipes with nitrogen
or dry air, to remove any dust or foreign materials before
connecting pipes.
N O T E
5HIHUWR,QVWDOODWLRQDQG2SHUDWLRQ0DQXDORIWKHRXWGRRUXQLWIRUGHWDLO
RQDOORZDEOHSLSHOHQJWK
N O T E
• 1RWLFHIRUUHIULJHUDQWSLSHHQGV
• $WWDFKDFDSRUSXWDSODVWLFEDJRYHUWKHSLSHHQG
In case of getting the pipe through a hole in the wall.
Attach a cap or put a plastic bag
Correct
Incorrect
Hole
Hole
Cap or plastic bag
Do not place the pipe directly on the ground.
Correct
Incorrect
Cap or plastic bag
In case of rain
Correct Incorrect
c
Rubber Band
Rain water
can come in.
Correct
Incorrect
Rain water can
come in
Rubber band
Cap or plastic bag
• 'XH WR WKH FKDQJH RI UHIULJHUDQW RLO WKH UHIULJHUDQW F\FOH LV PRUH
VXEMHFWWRWKH HQWUDQFH RI IRUHLJQ PDWWHUV VXFK DVPRLVWXUH R[LGH
¿OP DQG JUHDVH %H FDUHIXO WKDW WKHVH VXEVWDQFHV GR QRW HQWHU
WKH UHIULJHUDQW F\FOH GXULQJ LQVWDOODWLRQ ZRUN 2WKHUZLVH WKH\ PD\
EH WUDSSHG LQWR VXFK SDUWV DV WKH H[SDQVLRQ YDOYH KLQGHULQJ WKH
RSHUDWLRQ
Refrigerant piping
PMML0363A rev.2 - 08/2016 - P541655922