16.4 ELECTRICAL WIRING CAPACITY
16.4.1 )LHOGPLQLPXPZLUHVL]HVIRUSRZHU
VRXUFH
Use an ELB (Earth Leakage Breaker). If not used, it will
FDXVHDQHOHFWULFVKRFNRUD¿UH
Do not operate the system until all the check points have
been cleared:
Check to ensure that the electrical resistance is more
than 1 megohm, by measuring the resistance between
ground and the terminal of the electrical parts. If it is
less than 1 megohm, do not operate the system until the
electrical leakage is found and repaired.
Check to ensure that the stop valves of the outdoor unit
are fully opened, and then start the system.
Check to ensure that the switch on the main power
source has been ON for more than 12 hours, to warm the
compressor oil by the crankcase heater.
Do not touch any of the parts by hand at the discharge gas
side, since the compressor chamber and the pipes at the
discharge side are heated higher than 90ºC.
Model Power source Maximum current
3RZHUVRXUFHFDEOHVL]H
IEC 60335-1
7UDQVPLWWLQJFDEOHVL]H
IEC 60335-1
RCIM-0.6FSN4
RCIM-0.8FSN4
RCIM-1.0FSN4
RCIM-1.5FSN4
RCIM-2.0FSN4
RCIM-2.5FSN4
1~ 230V 50Hz 5A 0.75mm
2
0.75mm
2
N O T E
)ROORZWKHORFDOFRGHVDQGUHJXODWLRQVZKHQVHOHFWLQJ¿HOGZLUHV
7KHZLUHVL]HVLQWKHWDEOHDUHVHOHFWHGDWWKHPD[LPXPFXUUHQWRIWKH
XQLWDFFRUGLQJWRWKH(XURSHDQ6WDQGDUG,(&8VHWKHZLUHV
ZKLFKDUHQRWOLJKWHUWKDQWKHRUGLQDU\WRXJKUXEEHUVKHDWKHGÀH[LEOH
FRUG FRGH GHVLJQDWLRQ +51) RU RUGLQDU\ SRO\FKORURSUHQH
VKHDWKHGÀH[LEOHFRUGFRGHGHVLJQDWLRQ+51)
8VH D VKLHOGHG FDEOH IRU WKH WUDQVPLWWLQJ FLUFXLW DQG FRQQHFW LW WR
JURXQG
,QWKHFDVHWKDWSRZHUFDEOHVDUHFRQQHFWHGLQVHULHVDGGPD[LPXP
FXUUHQWWRHDFKXQLWDQGVHOHFWZLUHVEHORZ
Selection according to IEC 60335-1
Current i (A) Wire size (mm
2
)
i < 6 0.75
6 < i < 10 1
10 < i < 16 1.5
16 < i < 25 2.5
25 < i < 32 4
32 < i < 40 6
40 < i < 63 10
63 < i *3
,QWKHFDVHWKDWFXUUHQWH[FHHGV$GRQRWFRQQHFWFDEOHVLQVHULHV
16.4.2 'HWDLOVRIHOHFWULFDOZLULQJFRQQHFWLRQ
The electrical wiring capacity of the outdoor unit should be referred according to Installation and Operation Manual of the outdoor
unit. Setting Dip Switch may be required depending on the combination with the outdoor unit.
([DPSOHIRU8723,$6HULHV
The control cable length between the outdoor unit and the indoor unit shall be less than 75m.
Case A
Power source type: 3 Phase 4 Wires
Ty
A B 1 2
1~
230V / 50Hz
*7
*4
*5
ELB
L2
N
1 2
R
L1
S
N
L1
L1
A B 1 2
*7
*4
*4
*5
L2
1 2
L1
*4
*8
*8
Remote control switch cable (Field-Supplied)
Shielded twist pair Cable 0.75mm
2
This cable does not need any polarity.
'RQRWDSSO\DQH[FHVVLYHO\KLJKYROWDJH
to this cable. (Rated Voltage: 5V)
Power source cable
Pay attention to the phase of
power source when wiring.
Control cable
Shielded twist pair cable 0.75mm
2
This cable does not need any polarity. Do not apply an
H[FHVVLYHO\KLJKYROWDJHWRWKLVFDEOH5DWHG9ROWDJH9
Remote control
switch (option)
Indoor unit
Outdoor unit
* Main
switch
Earth
wiring
Earth wiring
(*) Refer to Installation and Operation Manual of connected outdoor unit for details of wire, ELB and main switch.
Electrical wiring
PMML0363A rev.2 - 08/2016 - P541655929