TROUBLESHOOTING
Troubleshooting
Problem Causes Solution
No Activation of
Unit Operation
Indicator
Electrical Power Source Failure Wait for Recovering of Electrical Power Supply
Blow off Main
Switch Fuse
Electrical Short Circuit to Earth
Replace the Main Switch Fuse after Eliminating
Earthing
Faulty Compressor Motor Replace the Compressor and the main Switch Fuse
Faulty Indoor Fan Motor
Replace the indoor Fan Motor and the Main Switch
Fuse
Blow off
Control
Circuit Fuse
Electrical Short Circuit between Different Phase
Wires
Replace the Fuse
Electrical Short Circuit to Earth Replace the Fuse
Faulty Magnetic Switch for Compressor Motor Replace the magnetic Switch and the Fuse
Faulty Transformer of Indoor Unit
Replace the Transformer
Disconnected Cable of Remote Control Panel to the Indoor Unit Replace the Cable
Abnormality of Remote Control Switch
Check the connection of the Remote Control Cable.
Replace the Remote Control Switch.
Incorrect
activation of
PCB
Disconnected Wire(s) to PCB of Indoor Unit Connect Wire(s) to the PCB
Faulty PCB of Indoor Unit Replace the PCB of Indoor Unit
No Activation of
Compressor and
Fan Motor (In the
Case of Indicator
Activation of
Remote Control
Switch)
Faulty Indoor Fan Motor Replace the Indoor Fan Motor
Faulty Outdoor Fan Motor Replace the Outdoor Fan Motor
Faulty magnetic switch for Outdoor Fan Motor Replace the magnetic switch of the Outdoor Unit
Faulty Compressor Motor of Compressor Replace the Compressor
Faulty Magnetic Switch for Compressor Motor Replace the magnetic switch
Incorrect activation of PCB
Disconnected Wire(s) to PCB Connect Wire(s) to the PCB
Faulty PCB of Indoor Unit Replace the PCB for Indoor Unit
In case of 3~ unit installed
for first time, if an “05” code
is indicated on remote
control switch
Phase protection Relay
Switch off the power supply of the unit, reverse 2 of
the phases, reapply the power and restart the unit
Flickering of
Indicator and Lamp
of “RUN” Switch
Faulty Internal Thermostat for Indoor Fan Motor
Replace the Indoor Fan Motor
Disconnected Wires between Indoor Unit and Outdoor Unit Connect the Wires Correctly
Incorrect Activation of PCB
Disconnected Wire(s) to the PCB Connect Wire(s) to the PCB
Faulty PCB of Indoor Unit Replace the PCB for Indoor Unit
Tripped Float Switch for Drain (only in RCI Units)
Adjust level of the Drain pan Repair or Replace the
Drain Discharge Mechanism. Remove the Clogged
Material
No Speed Change
of Fan In spite of
Adjustment
Abnormality of Thermistor
for Air Inlet Discharge Temp.
Faulty Thermistor
Replace the Thermistor
Disconnected Wire of Thermistor
Connect the Wire to the Thermistor
Faulty Remote Control Switch Replace the Remote Control Switch
Faulty PCB of Indoor Unit Replace the PCB of the Indoor Unit
No Stopping
and Starting of
Compressor In
spite of Adjusting
Thermostat
Abnormality of Thermistor
for Air Inlet Temperature
Faulty Thermistor
Replace the Thermistor
Disconnected Wire of Thermistor
Connect the Wire of Thermistor
Faulty “TEMP” Switch of Remote Control Switch Replace “TEMP” Switch of Remote Control Switch
Faulty PCB of Indoor Unit Replace PCB of the Indoor Unit
Faulty Cable of Remote Control Switch Replace the Cable