TROUBLESHOOTING
Problem Causes Solution
No Restarting of
Outdoor Fan Motor
and Compressor
after Stoppage
for Cooling
Operation (Lamp
of “RUN” Switch
and Indicator is
Flickered)
Tripped High Pressure
Switch
Obstacle to Air Intake of Air Discharge
for Outdoor Unit
Remove the obstacle
Insufficient Air Intake or Air Discharge
Space for Outdoor Unit
Keep the minimum Air Intake and Air Discharge Space
Short Circuited Air Discharge for
Outdoor Unit
Remove Any Obstacle
Faulty Outdoor Fan Motor Replace the Outdoor Fan Motor
Overcharged Refrigerant Charge Correct Refrigerant Gas
Clogged Capillary Tube Replace the Capillary Tube
Excessively High Ambient
Temperature
See Unit Working Range
Temperature of High Air Inlet
Temperature for Indoor Unit
Reduce the Cooling Load
Tripped Overcurrent
relay for Compressor
Motor
Excessively High Discharge or Suction
Pressure
Same as Tripped High Pressure Switch Remedy Action
High or Low Voltage
Obtain Correct Voltage
Faulty Compressor Motor (After
Checked Electrical Resistance)
Replace the Compressor
Faulty Overcurrent Relay Replace the Overcurrent Relay
Faulty Starting Relay Replace the Starting Relay
Frequent start/stop compressor Replace the compressor
Insufficient Cooling
(Lamp of “RUN”
Switch activates)
Excessive Cooling Load Reduce the Cooling Load
Too Low Pressure
Insufficiently Charged Refrigerant Gas
Charge Correct Refrigerant Gas
Refrigerant Gas Leakage Repair Leakage and Charge Correct Refrigerant Gas
Clogged Strainer Repair or Replace the Strainer
Clogged Suction Piping Remove the Obstacle
Clogged Air Filter Cleaning the Air Filter
Obstacle to Air Intake or Air Discharge
for Indoor Unit
Take Away the Obstacle
Faulty Indoor Fan Motor Replace the Indoor Fan Motor
Short Circuited Air Discharge for
Indoor Unit
Take Away any Obstacle
Excessively High
Pressure
Same as Tripped Air Discharge for
Indoor Unit
Same as Tripped High Pressure Switch Remedy Action
Insufficient Heating
(Lamp of “RUN”
Switch Activates)
(Only for Heat-
Pump Models)
Too Low Pressure
Clogged Strainer Repair or Replace the Strainer
Clogged Suction Piping Remove the Obstacle
Obstacle to Air Intake or Air Discharge
for Outdoor Unit
Take away the obstacle
Faulty Outdoor Fan Motor Replace the Outdoor Fan Motor
Short Circuited Air Discharge for
Outdoor Unit
Take Away any Obstacle
Faulty Thermistor(s) for Deicer
Replace the Thermistor(s)
Excessively High
Pressure
Same as Tripped Air Discharge for
Indoor Unit
Same as Tripped High Pressure Switch Remedy Action