4.6  SERVICE AND OPERATION SPACE FOR RPI-(4.0~6.0)FSRE
? NOTE
A service access from the bottom side is required for servicing and maintenance.
4.6.1  Service space for electrical box
a
b c d
e
e
f
Electrical 
box
Top view
Service space (mm)
a b c d e f
800 300 1474 100 1000 657
4.6.2   Service space for lower extraction of the 
air lter
a
b
Service space (mm)
a b
1420 200
4.6.3   Service space for lateral extraction of the 
air lter
a
b
Service space (mm)
a b
500 500
4.6.4  Operation space
! CAUTION
•  If the suction of the indoor unit is through a plenum, there must be no 
obstacle less than 1000mm.
•  If the indoor unit is discharged freely, there must be no obstacle less 
than 1000mm.
•  In case of suction or discharge of the indoor unit through ducts, ducts 
must be straight 1000mm span from the unit.
a'
b'
Top side
Bottom side
c'
d'
Operation space (mm)
a' b' c' d'
20 10 10 300