7.1  WIRING CONNECTION
! CAUTION
Use twisted shielded pair cable or shield pair cable for transmission wires 
between the indoor and the outdoor units, and connect the shielded part 
to the earth screw in the electrical box of the indoor unit.
7.1.1  Electrical box location
The service panel for the fan motor of the indoor unit is provided 
at the bottom side of the unit, and the service panel for the 
electrical box is provided at the left side of the unit as shown 
below.
RPI-(1.5-6.0)FSRE
Wiring 
connection
Liquid pipe
Gas pipe
Drain hose
Electrical 
box
7.1.2  Electrical wiring installation
1  Open the bottom side Service Panel.
2  Cut out the centre of the rubber bushing in the wiring 
connection hole of the unit showed above and of the 
electrical box shown below.
3  Connect the power supply and ground wires to the terminals 
in the electrical box as shown below.
Earth
Earth
Power 
supply
Control
4  Connect the wires between the indoor unit and the outdoor 
unit to the terminals 1 and 2 in the electrical box.
5  Connect the cable of the Remote Control Switch to the 
terminals A and B in electrical box.
6  Tightly x the wires with the cord clamp inside the indoor 
units.
7  Seal the wiring connection hole after running the cables 
with the seal material (cover plate) to protect the unit from 
condensed water and insects.
! CAUTION
Use twisted shielded pair cable or shield pair cable for transmission wires 
between the indoor and the outdoor units, and connect the shielded part 
to the earth screw in the electrical box of the indoor unit as shown in the 
gure.
7.1.3  Electrical box layout
Electrical box
TB
PCB
PCB: Printed circuit board
7.1.4  Terminal board connections
Earth Screw
Power supply wires 
(Single phase)
Transmission 
wires
Remote control 
(PC-ARFP1E)
ELECTRICAL WIRING
PMML0528 rev.1 - 02/2021
20