NOTE
Some refrigerant charge calculations differ when installing
Wall Type (RPK-FSNH3M Series) with the expansion valve
kit. Refer to the item Additional refrigerant calculation for wall
type (RPK-FSNH3M Series) with the expansion valve kit.
Ensure that the total additional charge quantity should not ex-
ceed the max. additional refrigerant charge quantity shown in
the table on the next page.
Maximum additional refrigerant charge quantity
HP (5-10) 12
(12/16-P)
(14/16)
(18-24)
(24/32-P)
(26-54)
Maximum addi-
tional refrigerant
charge quantity
(kg)
28.0 36.0 40.0 51.0 63.0
Charging work
Charge the system with refrigerant R410A.
Record of additional charge
Total refrigerant charge of this system is calculated in the follow-
ing formula.
Total refrigerant charge = W + W0
This system
= + = kg
Total additional charge:
W kg
Total refrigerant charge:
kg
Date of refrigerant charge work:
/ /
Refrigerant charge amount of outdoor unit
before shipment (W0) kg
Model
W0 Outdoor
unit refrigerant
charge (kg)
Model
W0 Outdoor
unit refrigerant
charge (kg)
RAS-
8FSXN1E
5.4
RAS-
5FSXNH(E)
5.6
RAS-
10FSXN1E
6.4
RAS-
6FSXNH(E)
5.6
RAS-
12FSXN1E
7.3
RAS-
8FSXNH(E)
7.7
RAS-
14FSXN1E
8.5
RAS-
10FSXNH(E)
7.7
RAS-
16FSXN1E
9.5
RAS-
12FSXNH(E)
8.3
NOTE
W0 is outdoor unit refrigerant charge before shipment.
In case of the combination of the base units, calculate the
total refrigerant charge before shipment of the outdoor units
to be combined.
Regarding the uorocarbon, follow the specication label or re-
frigerant label attached to the product. After the additional re-
frigerant charge, record the total refrigerant (= refrigerant before
shipment + additional refrigerant in the eld) in the refrigerant
label (*).
(*): In case of the combination of base units, record the total re-
frigerant in the main unit label.
NOTE
When the refrigerant is recovered or charged because of
repairing, operating or adjusting the unit, record the refrigerant
quantity again.
NOTE
Emissions of the uorocarbons without any reason are pro-
hibited.
For disposal and maintenance of this product, collection of
uorocarbons is required.
Additional refrigerant calculation for wall type
(RPK-FSNH3M Series) with the expansion valve kit
The additional refrigerant calculation for wall type (RPK-FSNH3M
Series) with the expansion valve kit is as follows. Refer to the
item Calculating method of additional refrigerant charge W1.
Firstly calculate the additional refrigerant amount for the liquid
pipe between Multi-Kit and the expansion valve kit according to
the piping length and diameter.
Then, calculate the additional refrigerant amount for the liquid
pipe between indoor unit and the expansion valve kit (Pipe diam-
eter: 6.35 refrigerant amount for 1m pipe: 0.011kg/m).
L< 15m6.35
15 ~ 30m9.52
3 ~ 5m
Ø6.35
Calculate the additional
refrigerant charge quantity
depending on the piping
length and the piping size
Calculate the additional
refrigerant charge quantity.
“0.011” kg per 1 m
Indoor unit
Expansion
valve kit
Multi kit (liquid line)
Liquid line
NOTE
Refer to the table System Combination for the number of indoor
units and the expansion valve kit connectable to the outdoor unit.
52
PMML0294A rev.2 - 07/2014
Additional refrigerant charge
PMML0294A_rev.2_02-2014.indb 52 14/07/2014 12:28:31