Nut pre-assembly prior to leveling unit
Nut (eld-supplied)
Sling bolt (eld-supplied)
Washer with insulation (accessory)
Approx.
45
Surface of ceiling
Suspension bracket
(attached indoor unit)
Washer (accessory)
Nut (eld-supplied)
Approx.
50
Suspend the indoor unit using the following steps
1 Hook suspension bracket to the nut and washer of each
sling bolt, as shown, starting from one side.
2 Check the nut and washer are correctly xes by the retainers
of the suspension bracket.
3 Hook the suspension bracket of the other side to nut and
washer.
Sling bolt
Washer
Suspension bracket
Inlet air
Nut
Washer with insulation
Nut
? NOTE
Make sure to use washers (accessories) for xing the suspension bolts to
the suspension brackets. The washer with insulation must be tted with
the insulation side downward to facilitate hanging work.
4.3.2 Duct & suction air lter installation
Field Supply Duct installation
Fix the Flexible Air Duct to External Faces of unit anges (the
unit is equipped with factory supply anges for this purpose).
It is recommended to use a Flexible eld supply Duct portion in
order to avoid any abnormal sound vibration.
Insulate frame corners by using properly tape. Field supplied.
RPI units are equiped with standard Air Filter at the suction side.
This lter is provided for the cases in which no Suction Duct is
applied (or it is very short).
It is recommended the following indications depending on the
installation.
• Keep the standard Air Filter in case of no Suction Duct is
applied (g. 1).
• In case of applying Suction Duct, it is recommended to apply
Air Filter at the inlet point of Suction Duct, removing the
standard Air Filter of the unit (g. 2).
Fig. 1
Std. Air lter
(Factory supplied)
Air ow
Fig. 2
Air lter (Field supplied or
adapted factory supplied)
Air ow