1-17
TROUBLESHOOTING
1.2 Troubleshooting Procedure
   Alarm Code Indication of Remote Control Switch
1.2.1 Alarm Code Table
COOL
Indoor Unit
Number
Alarm Code
Indicated
for a second
alternately
MED
A/C
ADDS.  RN
ALARM
COOL
Connected No.
of Indoor Units
Alarm CodeModel Code
MED
A/C
ALARM
Code
No.
Category Content of Abnormality Leading Cause
01
 Indoor Unit  Tripping of Protection Device
 High Water Level in Drain Pan,
 Activated Float Switch.
02
Outdoor Unit
 Tripping of Protection Device
 (Except Alarm Code 41 and 42)
 Activated High Pressure Switch.
 Locked Motor in Cooling Operation.
03
 Abnormality between Indoor and Outdoor
 Incorrect Wiring.  Loose Terminals,
 Disconnected wire, Tripping of Fuse.
04
 Abnormality between Inverter and Control PCB  Failure in Transmission of PCB for Inverter.
06
Voltage Drop
 Voltage Drop by Excessively Low or High
 Voltage to Outdoor Unit
 Voltage Drop of Power Supply
 Insufficient Capacity of Power Supply Wiring.
07
 Decrease of Discharge Gas Superheat
 Discharge Gas SUPERHEAT less than
 10 deg. is maintained for one hour.
08
 Increase of Discharge Gas Temperature
 Temperature of the top of Compressor: Td
 Td    127
o
C(Cooling), Td    120
o
C(Heating)
 over 10 minutes, or  Td    140
o
C over 5 seconds.
11
 Inlet Air Thermistor
12
 Outlet Air Thermistor
13
 Freeze Protection Thermistor
14
 Gas Piping Thermistor
19
 Tripping of Protection Device
 Activated Internal Thermo of Fan Motor.
20
 Compressor Thermistor
22
 Outdoor Air Thermistor
24
 Evaporating Thermistor
31
 Incorrect Capacity of Outdoor and Indoor Unit
 Incorrect Setting of Capacity Combination or
 Incorrect O.U. Capacity Setting.
35
 Incorrect Indoor Unit No. Setting  Duplication of Indoor Unit No.
36
 Incorrect Combination of Indoor Unit
 FSG2E series connects to HVRG series outdoor unit
 (European Area Only).
 HRG series of the indoor unit is connected to FSG(1)
 and FXG(1) series outdoor units (European Area Only).
38
 Abnormality of Protective Circuit in outdoor Unit  Failure of Protection detecting Circuit
41
 Overload cooling
 (Possibility of high pressure device activation.)
 O.U. Pipe Thermistor Temp. is Higher than 55
o
C
 and the Comp. Top Temp. is Higher than 95
o
C
 when O.U. Protection Device is activated.
42
 Overload heating
 (Possibility of high pressure device activation.)
 I.U. Freeze Protection Thermistor Temp. is Higher
 than 55
o
C and the Comp. Top Temp. is Higher than
 95
o
C when O.U. Protection Device is activated.
47
 Activation of Low Pressure Decrease
 Protection Device
 Stoppage by Excessively Decrease of evaporating
 Temperature ( Te    -35
o
C) is activated 3 times in
 one hour,  Locked Motor in Heating Operation.
51
 Abnormality of Current Sensor for Inverter
 Failure of Control PCB, ISPM
52
 Activating Overcurrent Protection  Failure of ISPM, Clogging of Heat Exchanger.
53
 Activating Protection of ISPM
 ISPM Abnormality
 Failure of Compressor, clogging of Heat Exchanger.
54
 Inverter Fin Temperature Increase
 Abnormal Inverter Fin Thermistor,
 Clogging of Heat Exchanger
 Abnormal Outdoor Fan
57
Outdoor Fan  Fan Motor Abnormality
 Disconnected wire or Incorrect wiring between
 Control PCB and Inverter PCB.
 Incorrect Wiring or Fan Motor Abnormality
EE
Compressor  Compressor Protection Alarm  Failure of Compressor.
Inverter
Transmission
 Failure of Thermistor, Loose Terminal,
 Disconnected Wire.
 Locked Motor in Heating Operation.
Sensor on
Outdoor Unit
Pressure
Cycle
Sensor on
Indoor Unit
 Failure of Thermistor, Loose Terminal,
 Disconnected Wire.
System
> >
>
<