1. Overview
HCC-95P(-Ex) Series is a capacitance type level switch and it detects a level of
medium by sensing of capacitance value change by dielectric constant of each
medium.
2. Operating Principle & Composition
When an air surrounding the electrode probe is replaced by other medium,
the capacitance value is changed according to the dielectric constant of the
medium. Once the electrode probe is touched by the medium, the capacitance
value is increased and the level switch activates relay output by converting of
the changed capacitance value to the electronic signal.
2
3. Specification
■ Weather-Proof Version
Model HCC-95P HCC-95PH HCC-95PW HCC-95PWH
Probe Type Rod(Flat) Rope
Mounting Screw or Flange
Ambient Temperature -20°C ~ +60°C
Process Temperature -40°C ~ +80℃ -40°C ~ +150℃ -40°C ~ +80℃ -40°C ~ +150℃
Process Pressure Vacuum~ 20kg/cm2(300#)
Power Source AC 90~240V, 50/60Hz (Std.), DC +24V (Opt.)
Output DPDT
Contact Rating AC 250V, 5A / DC 30V, 5A
Enclosure Weather-Proof (IP65)
Wetted Parts Material SUS 304, 316L with Teflon(Peek) SUS 304, 316L with Teflon
Process Connection PT 1”(M) Screw
Housing ; Cable Entry
PBT;PF1/2”(F),IP65
AL;PF1/2”(F),IP66
PBT;PF1/2”(F),IP65
AL;PF1/2”(F),IP66
AL;PF1/2”(F),IP66 AL;PF1/2”(F),IP66
■ Ex-Proof Version
Model HCC-95P-Ex HCC-95PH-Ex HCC-95PW-Ex HCC-95PWH-Ex
Probe Type Rod(Flat) Rope
Mounting Screw or Flange
Ambient Temperature -20°C ~ +60°C
Process Temperature -40°C ~ +80℃ -40°C ~ +150℃ -40°C ~ +80℃ -40°C ~ +150℃
Process Pressure Vacuum~ 20kg/cm2(300#)
Power Source AC 90~240V, 50/60Hz (Std.) / DC +24V (Opt.)
Output DPDT
Contact Rating AC 250V, 5A / DC 30V, 5A
Enclosure
Ex-proof Ex d IIC T5/T6(*), IP66 Ex d IIC T3/T4(*), IP66 Ex d IIC T5/T6(*), IP66 Ex d IIC T3/T4(*), IP66
Dust-proof Ex tD A21 IP66 T80℃ Ex tD A21 IP66 T150℃ Ex tD A21 IP66 T80℃ Ex tD A21 IP66 T150℃
Wetted Parts Material SUS 304, 316L with Teflon(Peek) SUS 304, 316L with Teflon
Process Connection PT 1”(M) Screw
Housing ; Cable Entry AL. ; PF 1/2”(F), IP66
(*) Explosion-proof Fluid Temp. & Grade: Max. 70℃ for T6
Max. 80℃ for T5
Max. 130℃ for T4
Max. 150℃ for T3